What are the four main components of a vapour compression refrigeration system?
Show answer & solution
Answer: (C) Compressor, condenser, expansion device and evaporator
The refrigerant circulates through all four.
Mechanical Engineering · Refrigeration & Air Conditioning
38 questions, each with the answer and a worked solution.
Practice interactively and track your score →What are the four main components of a vapour compression refrigeration system?
Answer: (C) Compressor, condenser, expansion device and evaporator
The refrigerant circulates through all four.
What is the condition of the refrigerant immediately after the expansion valve?
Answer: (D) A low-pressure, low-temperature wet vapour
Some liquid flashes into vapour during throttling.
What is the condition of the refrigerant between the expansion valve and the evaporator?
Answer: (C) A wet vapour (mixture of liquid and vapour)
It then evaporates fully while absorbing heat.
What is the condition of the refrigerant as it enters the compressor in a simple saturated cycle?
Answer: (A) Dry saturated vapour
Liquid entering a reciprocating compressor can damage it.
What is the condition of the refrigerant leaving the compressor?
Answer: (B) High-pressure superheated vapour
It then enters the condenser.
What is the condition of the refrigerant leaving the condenser in a simple cycle?
Answer: (C) High-pressure saturated (or subcooled) liquid
It then flows to the expansion device.
Where is the highest temperature in a vapour compression cycle?
Answer: (A) At the compressor discharge
Compression raises the vapour temperature above condensing temperature.
Where is the lowest temperature in a vapour compression cycle?
Answer: (B) In the evaporator
The evaporator absorbs heat from the cooled space.
What process takes place in the expansion valve?
Answer: (D) Throttling at constant enthalpy, reducing pressure and temperature
No work is done during throttling.
What is the advantage of dry compression over wet compression in reciprocating compressors?
Answer: (C) It prevents liquid damage to the compressor and gives a larger refrigerating effect per kilogram
Wet vapour can wash lubricant off cylinder walls.
What does a horizontal line on a pressure–enthalpy (p–h) chart represent?
Answer: (A) A constant-pressure process
Evaporation and condensation appear as horizontal lines.
What does a vertical line on a pressure–enthalpy chart represent?
Answer: (D) A constant-enthalpy (total heat) process
Throttling in the expansion valve appears as a vertical line.
Why are condensation and desuperheating shown as a single horizontal line on a p–h diagram?
Answer: (B) Both occur at constant condenser pressure
The superheated vapour first cools, then condenses.
What does the lower horizontal line of a vapour compression cycle on a p–h chart represent?
Answer: (C) Evaporation of refrigerant in the evaporator
It occurs at low pressure.
What is subcooling (undercooling) of liquid refrigerant?
Answer: (A) Cooling the liquid below its condensing temperature before it enters the expansion valve
It increases the refrigerating effect.
What is the effect of subcooling on COP?
Answer: (D) It increases COP
More refrigerating effect is obtained for the same compressor work.
What is one purpose of subcooling the liquid refrigerant?
Answer: (B) To ensure that only liquid, not vapour, enters the expansion valve
Flash gas before the valve reduces capacity.
What is superheating of refrigerant vapour?
Answer: (D) Heating the vapour above its saturation temperature after evaporation
It ensures that no liquid reaches the compressor.
How does lowering the condenser temperature (with evaporator temperature constant) affect COP?
Answer: (C) COP increases
The compressor works against a smaller pressure ratio.
How does raising the evaporator temperature (with condenser temperature constant) affect COP?
Answer: (A) COP increases
The temperature lift is reduced.
How does lowering the evaporator temperature affect compressor power per tonne of refrigeration?
Answer: (B) It increases
A larger pressure ratio needs more work.
What is the effect of reducing suction pressure on a vapour compression system?
Answer: (B) Refrigerating capacity falls, specific volume of suction vapour rises and power per tonne increases
Low suction pressure is undesirable for efficiency.
For a high COP, what should the pressure range between evaporator and condenser be?
Answer: (C) As small as possible
A smaller temperature lift needs less work.
Why is the suction pipe of a refrigeration compressor larger in diameter than the delivery pipe?
Answer: (A) The low-pressure suction vapour has a much larger specific volume
Larger pipes keep pressure drop low.
Why should the highest pressure and temperature in a refrigeration cycle be well below the critical values?
Answer: (D) Near the critical point, latent heat becomes very small and the cycle becomes inefficient
A refrigerant must condense at the condenser temperature.
How does the latent heat of vaporisation of a refrigerant change at lower temperatures and pressures?
Answer: (B) It increases
Latent heat becomes zero at the critical point.
How do non-condensable gases such as air in the system affect condensing pressure?
Answer: (C) They raise the condensing pressure
Purging removes them.
What is flash gas in a refrigeration system?
Answer: (A) Vapour formed when liquid refrigerant passes through the expansion valve or loses pressure in the liquid line
Flash gas reduces the refrigerating effect.
What is a multi-stage vapour compression system used for?
Answer: (D) Obtaining very low evaporator temperatures efficiently, with intercooling between stages
Single-stage compression becomes inefficient at large pressure ratios.
What is a cascade refrigeration system?
Answer: (D) Two or more refrigeration cycles with different refrigerants, where the condenser of one cools the evaporator of the next
It is used for very low temperatures.
What happens to refrigerating capacity when condenser temperature rises?
Answer: (B) It decreases
High ambient temperatures reduce AC capacity.
What happens to compressor power when condenser pressure rises?
Answer: (C) It increases
The compressor works against a higher pressure ratio.
What is the work of compression in a vapour compression cycle on a p–h chart?
Answer: (A) The enthalpy difference between compressor outlet and inlet
COP = refrigerating effect ÷ compression work.
In a vapour compression cycle, the enthalpy at compressor inlet is 400 kJ/kg, at compressor outlet 430 kJ/kg, and at evaporator inlet 250 kJ/kg. What is the COP?
Answer: (C) 5
COP = (400 − 250)/(430 − 400) = 150/30.
What is the refrigerating effect in the previous example (h₁ = 400 kJ/kg, evaporator inlet = 250 kJ/kg)?
Answer: (B) 150 kJ/kg
Refrigerating effect = h₁ − h₄.
Why is a liquid–suction heat exchanger used in some systems?
Answer: (D) To subcool the liquid and superheat the suction vapour, preventing liquid from reaching the compressor
It improves performance with some refrigerants.
What is the main reason for frequent compressor cycling in an oversized air conditioner?
Answer: (A) It reaches the set temperature too quickly and switches off often, also removing less moisture
Correct sizing improves comfort and efficiency.
What happens if a refrigeration system is undercharged with refrigerant?
Answer: (B) Cooling capacity drops and the evaporator may partly ice up
Leaks are the usual cause.