Question 1

What are the four main components of a vapour compression refrigeration system?

  1. Boiler, turbine, condenser and pump
  2. Generator, absorber, pump and condenser
  3. Compressor, condenser, expansion device and evaporator
  4. Fan, filter, heater and duct
Show answer & solution

Answer: (C) Compressor, condenser, expansion device and evaporator

The refrigerant circulates through all four.

Question 2

What is the condition of the refrigerant immediately after the expansion valve?

  1. A high-pressure gas
  2. A high-pressure liquid
  3. A superheated vapour
  4. A low-pressure, low-temperature wet vapour
Show answer & solution

Answer: (D) A low-pressure, low-temperature wet vapour

Some liquid flashes into vapour during throttling.

Question 3

What is the condition of the refrigerant between the expansion valve and the evaporator?

  1. High-pressure liquid
  2. Pure liquid
  3. A wet vapour (mixture of liquid and vapour)
  4. Superheated vapour
Show answer & solution

Answer: (C) A wet vapour (mixture of liquid and vapour)

It then evaporates fully while absorbing heat.

Question 4

What is the condition of the refrigerant as it enters the compressor in a simple saturated cycle?

  1. Dry saturated vapour
  2. Wet vapour with much liquid
  3. Subcooled liquid
  4. Saturated liquid
Show answer & solution

Answer: (A) Dry saturated vapour

Liquid entering a reciprocating compressor can damage it.

Question 5

What is the condition of the refrigerant leaving the compressor?

  1. Low-pressure liquid
  2. High-pressure superheated vapour
  3. Wet vapour
  4. Subcooled liquid
Show answer & solution

Answer: (B) High-pressure superheated vapour

It then enters the condenser.

Question 6

What is the condition of the refrigerant leaving the condenser in a simple cycle?

  1. Dry saturated vapour at low pressure
  2. Superheated vapour
  3. High-pressure saturated (or subcooled) liquid
  4. Low-pressure wet vapour
Show answer & solution

Answer: (C) High-pressure saturated (or subcooled) liquid

It then flows to the expansion device.

Question 7

Where is the highest temperature in a vapour compression cycle?

  1. At the compressor discharge
  2. In the evaporator
  3. After the expansion valve
  4. At the condenser outlet
Show answer & solution

Answer: (A) At the compressor discharge

Compression raises the vapour temperature above condensing temperature.

Question 8

Where is the lowest temperature in a vapour compression cycle?

  1. At the compressor discharge
  2. In the evaporator
  3. In the condenser
  4. At the receiver
Show answer & solution

Answer: (B) In the evaporator

The evaporator absorbs heat from the cooled space.

Question 9

What process takes place in the expansion valve?

  1. Constant-temperature condensation
  2. Isentropic compression
  3. Constant-pressure heating
  4. Throttling at constant enthalpy, reducing pressure and temperature
Show answer & solution

Answer: (D) Throttling at constant enthalpy, reducing pressure and temperature

No work is done during throttling.

Question 10

What is the advantage of dry compression over wet compression in reciprocating compressors?

  1. It needs no compressor
  2. It reduces the condenser size to zero
  3. It prevents liquid damage to the compressor and gives a larger refrigerating effect per kilogram
  4. It lowers discharge temperature to the evaporator temperature
Show answer & solution

Answer: (C) It prevents liquid damage to the compressor and gives a larger refrigerating effect per kilogram

Wet vapour can wash lubricant off cylinder walls.

Question 11

What does a horizontal line on a pressure–enthalpy (p–h) chart represent?

  1. A constant-pressure process
  2. A constant-enthalpy process
  3. A constant-entropy process
  4. A constant-temperature process only in superheat
Show answer & solution

Answer: (A) A constant-pressure process

Evaporation and condensation appear as horizontal lines.

Question 12

What does a vertical line on a pressure–enthalpy chart represent?

  1. A constant-entropy process
  2. A constant-pressure process
  3. A constant-volume process
  4. A constant-enthalpy (total heat) process
Show answer & solution

Answer: (D) A constant-enthalpy (total heat) process

Throttling in the expansion valve appears as a vertical line.

Question 13

Why are condensation and desuperheating shown as a single horizontal line on a p–h diagram?

  1. Both occur at constant entropy
  2. Both occur at constant condenser pressure
  3. Both occur at constant enthalpy
  4. Both occur at constant volume
Show answer & solution

Answer: (B) Both occur at constant condenser pressure

The superheated vapour first cools, then condenses.

Question 14

What does the lower horizontal line of a vapour compression cycle on a p–h chart represent?

  1. Compression
  2. Throttling
  3. Evaporation of refrigerant in the evaporator
  4. Condensation
Show answer & solution

Answer: (C) Evaporation of refrigerant in the evaporator

It occurs at low pressure.

Question 15

What is subcooling (undercooling) of liquid refrigerant?

  1. Cooling the liquid below its condensing temperature before it enters the expansion valve
  2. Cooling the vapour in the compressor
  3. Heating the vapour above saturation
  4. Freezing the refrigerant
Show answer & solution

Answer: (A) Cooling the liquid below its condensing temperature before it enters the expansion valve

It increases the refrigerating effect.

Question 16

What is the effect of subcooling on COP?

  1. It has no effect
  2. It makes COP zero
  3. It decreases COP
  4. It increases COP
Show answer & solution

Answer: (D) It increases COP

More refrigerating effect is obtained for the same compressor work.

Question 17

What is one purpose of subcooling the liquid refrigerant?

  1. To heat the evaporator
  2. To ensure that only liquid, not vapour, enters the expansion valve
  3. To increase compressor work
  4. To reduce refrigerating effect
Show answer & solution

Answer: (B) To ensure that only liquid, not vapour, enters the expansion valve

Flash gas before the valve reduces capacity.

Question 18

What is superheating of refrigerant vapour?

  1. Cooling the liquid below condensing temperature
  2. Throttling the liquid
  3. Freezing the refrigerant
  4. Heating the vapour above its saturation temperature after evaporation
Show answer & solution

Answer: (D) Heating the vapour above its saturation temperature after evaporation

It ensures that no liquid reaches the compressor.

Question 19

How does lowering the condenser temperature (with evaporator temperature constant) affect COP?

  1. COP decreases
  2. COP stays the same
  3. COP increases
  4. COP becomes zero
Show answer & solution

Answer: (C) COP increases

The compressor works against a smaller pressure ratio.

Question 20

How does raising the evaporator temperature (with condenser temperature constant) affect COP?

  1. COP increases
  2. COP decreases
  3. COP becomes negative
  4. COP stays the same
Show answer & solution

Answer: (A) COP increases

The temperature lift is reduced.

Question 21

How does lowering the evaporator temperature affect compressor power per tonne of refrigeration?

  1. It becomes zero
  2. It increases
  3. It stays the same
  4. It decreases
Show answer & solution

Answer: (B) It increases

A larger pressure ratio needs more work.

Question 22

What is the effect of reducing suction pressure on a vapour compression system?

  1. There is no effect
  2. Refrigerating capacity falls, specific volume of suction vapour rises and power per tonne increases
  3. COP increases greatly
  4. Capacity rises and power falls
Show answer & solution

Answer: (B) Refrigerating capacity falls, specific volume of suction vapour rises and power per tonne increases

Low suction pressure is undesirable for efficiency.

Question 23

For a high COP, what should the pressure range between evaporator and condenser be?

  1. As large as possible
  2. Exactly double
  3. As small as possible
  4. It does not matter
Show answer & solution

Answer: (C) As small as possible

A smaller temperature lift needs less work.

Question 24

Why is the suction pipe of a refrigeration compressor larger in diameter than the delivery pipe?

  1. The low-pressure suction vapour has a much larger specific volume
  2. It is only for appearance
  3. The suction side carries liquid
  4. The delivery vapour is denser and colder
Show answer & solution

Answer: (A) The low-pressure suction vapour has a much larger specific volume

Larger pipes keep pressure drop low.

Question 25

Why should the highest pressure and temperature in a refrigeration cycle be well below the critical values?

  1. It increases COP
  2. It has no effect
  3. Above critical point condensation is easier
  4. Near the critical point, latent heat becomes very small and the cycle becomes inefficient
Show answer & solution

Answer: (D) Near the critical point, latent heat becomes very small and the cycle becomes inefficient

A refrigerant must condense at the condenser temperature.

Question 26

How does the latent heat of vaporisation of a refrigerant change at lower temperatures and pressures?

  1. It becomes zero
  2. It increases
  3. It decreases
  4. It stays the same
Show answer & solution

Answer: (B) It increases

Latent heat becomes zero at the critical point.

Question 27

How do non-condensable gases such as air in the system affect condensing pressure?

  1. They lower it
  2. They make it zero
  3. They raise the condensing pressure
  4. They have no effect
Show answer & solution

Answer: (C) They raise the condensing pressure

Purging removes them.

Question 28

What is flash gas in a refrigeration system?

  1. Vapour formed when liquid refrigerant passes through the expansion valve or loses pressure in the liquid line
  2. Air in the system
  3. Oil vapour
  4. Gas from a leak
Show answer & solution

Answer: (A) Vapour formed when liquid refrigerant passes through the expansion valve or loses pressure in the liquid line

Flash gas reduces the refrigerating effect.

Question 29

What is a multi-stage vapour compression system used for?

  1. Air conditioning of small rooms only
  2. Reducing COP
  3. Increasing evaporator temperature
  4. Obtaining very low evaporator temperatures efficiently, with intercooling between stages
Show answer & solution

Answer: (D) Obtaining very low evaporator temperatures efficiently, with intercooling between stages

Single-stage compression becomes inefficient at large pressure ratios.

Question 30

What is a cascade refrigeration system?

  1. An air cycle
  2. An absorption system
  3. A single cycle with two compressors in parallel
  4. Two or more refrigeration cycles with different refrigerants, where the condenser of one cools the evaporator of the next
Show answer & solution

Answer: (D) Two or more refrigeration cycles with different refrigerants, where the condenser of one cools the evaporator of the next

It is used for very low temperatures.

Question 31

What happens to refrigerating capacity when condenser temperature rises?

  1. It stays the same
  2. It decreases
  3. It increases
  4. It becomes infinite
Show answer & solution

Answer: (B) It decreases

High ambient temperatures reduce AC capacity.

Question 32

What happens to compressor power when condenser pressure rises?

  1. It stays the same
  2. It becomes zero
  3. It increases
  4. It decreases
Show answer & solution

Answer: (C) It increases

The compressor works against a higher pressure ratio.

Question 33

What is the work of compression in a vapour compression cycle on a p–h chart?

  1. The enthalpy difference between compressor outlet and inlet
  2. The enthalpy difference across the condenser
  3. The enthalpy difference across the evaporator
  4. The pressure difference only
Show answer & solution

Answer: (A) The enthalpy difference between compressor outlet and inlet

COP = refrigerating effect ÷ compression work.

Question 34

In a vapour compression cycle, the enthalpy at compressor inlet is 400 kJ/kg, at compressor outlet 430 kJ/kg, and at evaporator inlet 250 kJ/kg. What is the COP?

  1. 1.5
  2. 3
  3. 5
  4. 10
Show answer & solution

Answer: (C) 5

COP = (400 − 250)/(430 − 400) = 150/30.

Question 35

What is the refrigerating effect in the previous example (h₁ = 400 kJ/kg, evaporator inlet = 250 kJ/kg)?

  1. 30 kJ/kg
  2. 150 kJ/kg
  3. 250 kJ/kg
  4. 430 kJ/kg
Show answer & solution

Answer: (B) 150 kJ/kg

Refrigerating effect = h₁ − h₄.

Question 36

Why is a liquid–suction heat exchanger used in some systems?

  1. To heat the evaporator
  2. To remove oil
  3. To reduce condenser pressure
  4. To subcool the liquid and superheat the suction vapour, preventing liquid from reaching the compressor
Show answer & solution

Answer: (D) To subcool the liquid and superheat the suction vapour, preventing liquid from reaching the compressor

It improves performance with some refrigerants.

Question 37

What is the main reason for frequent compressor cycling in an oversized air conditioner?

  1. It reaches the set temperature too quickly and switches off often, also removing less moisture
  2. It has too little refrigerant
  3. It never reaches the set point
  4. It runs continuously
Show answer & solution

Answer: (A) It reaches the set temperature too quickly and switches off often, also removing less moisture

Correct sizing improves comfort and efficiency.

Question 38

What happens if a refrigeration system is undercharged with refrigerant?

  1. Capacity increases
  2. Cooling capacity drops and the evaporator may partly ice up
  3. Nothing changes
  4. The condenser freezes
Show answer & solution

Answer: (B) Cooling capacity drops and the evaporator may partly ice up

Leaks are the usual cause.