Which wiring system is most commonly used in modern Pakistani houses and offices?
Show answer & solution
Answer: (B) Concealed PVC conduit wiring
Conduits protect cables and allow rewiring.
Electrical Engineering · Utilisation & Electrical Installation
29 questions, each with the answer and a worked solution.
Practice interactively and track your score →Which wiring system is most commonly used in modern Pakistani houses and offices?
Answer: (B) Concealed PVC conduit wiring
Conduits protect cables and allow rewiring.
What is the IEC colour of the phase (line) conductor in single-phase installations?
Answer: (B) Brown
Older installations may use red.
What is the IEC colour of the neutral conductor?
Answer: (C) Blue
Older installations may use black.
What is the colour of the protective earth conductor under IEC standards?
Answer: (D) Green and yellow
Earth conductors must never be used for other purposes.
What cable size is typically used for domestic lighting circuits?
Answer: (B) 1.5 mm²
Socket circuits commonly use 2.5 mm² or larger.
What cable size is typically used for domestic socket outlet circuits?
Answer: (C) 2.5 mm²
Air conditioners and water heaters may need 4 mm² or more.
In which conductor must a single-pole switch be connected?
Answer: (A) The phase (line) conductor
Switching the neutral would leave the appliance live when off.
Which switching arrangement allows a staircase light to be controlled from two places?
Answer: (A) Two two-way switches
Intermediate switches are added for three or more positions.
Which switch is added between two two-way switches to control a light from three positions?
Answer: (D) Intermediate switch
It reverses the connections between the two travelling wires.
What is the maximum operating temperature of PVC-insulated cables?
Answer: (B) About 70 °C
XLPE-insulated cables can operate at about 90 °C.
Why must cable current ratings be derated when cables are grouped together or run in hot areas?
Answer: (D) Heat dissipation is reduced, so conductors could overheat at full rated current
Derating factors are given in installation standards.
What type of cable is commonly used for underground LV and MV power circuits?
Answer: (A) Steel wire armoured (SWA) cable
The armour gives mechanical protection.
What is the maximum voltage drop commonly recommended for LV final circuits under IEC 60364?
Answer: (C) About 3% for lighting and 5% for other uses
Excessive drop causes poor equipment performance.
What is the voltage drop in a 20 m single-phase circuit carrying 10 A with a conductor resistance of 0.01 Ω/m (each conductor)?
Answer: (C) 4 V
Total resistance = 2 × 20 × 0.01 = 0.4 Ω; drop = 10 × 0.4.
What is a distribution board (DB)?
Answer: (B) An enclosure housing the main switch, circuit breakers and RCDs that feed final circuits
Each final circuit has its own protective device.
What is the minimum insulation resistance generally required for LV circuits tested at 500 V DC?
Answer: (D) At least 1 MΩ
Low values indicate damaged or damp insulation.
Which test confirms that switches and fuses are connected in the phase conductor?
Answer: (A) Polarity test
Wrong polarity leaves equipment live when switched off.
What is earth fault loop impedance testing used for?
Answer: (B) Checking that fault current will be high enough to operate protective devices quickly
The loop includes the phase conductor, earth path and source.
Which rules, originally framed under the Electricity Act 1910, set safety requirements for electrical installations in Pakistan?
Answer: (C) Electricity Rules, 1937
They cover clearances, earthing and inspection of installations.
Why are three-pin sockets used for appliances with metal bodies?
Answer: (D) The third pin connects the appliance body to earth for safety
A fault to the body then trips the protective device.
What is a radial circuit?
Answer: (A) A final circuit that runs from the distribution board to outlets and ends at the last point
Ring circuits return to the board, allowing two paths.
What is trunking in electrical installations?
Answer: (A) An enclosed channel, often metal or PVC, for carrying several cables
It is used in offices and industrial buildings.
Why should aluminium and copper conductors not be connected directly together?
Answer: (B) Galvanic corrosion at the joint increases resistance and heating
Bimetallic connectors are used.
Which connection method is recommended for terminating large cables at switchgear?
Answer: (D) Crimped cable lugs bolted to terminals
Proper crimping ensures low-resistance joints.
Why must a separate circuit be provided for high-power appliances such as air conditioners?
Answer: (C) To avoid overloading general circuits and allow correctly rated protection
Each high-load appliance needs a suitable cable and breaker.
Why is the earth continuity conductor tested in new installations?
Answer: (A) To confirm a low-resistance path from exposed metal parts to the main earthing terminal
A broken earth leaves metal parts dangerous during faults.
What is the main advantage of conduit wiring over surface cleat wiring?
Answer: (C) Better mechanical protection, neater appearance and easy rewiring
Steel conduit also provides extra earthing and fire protection.
What is the purpose of a main switch at the consumer's distribution board?
Answer: (B) To isolate the entire installation from the supply
It is usually a double-pole switch or breaker.
What is the purpose of an earth electrode in a domestic installation?
Answer: (A) To connect the installation's earthing system to the general mass of earth
Pipe or rod electrodes are common.