Engineering, Management, Agriculture and Veterinary MCQs are now live. FPSC, PPSC, EPE, IELTS & GRE coming soon.

Utilisation & Electrical Installation: Wiring and Installation

Electrical Engineering · Utilisation & Electrical Installation

29 questions, each with the answer and a worked solution.

Practice interactively and track your score →
Question 1

Which wiring system is most commonly used in modern Pakistani houses and offices?

  1. Open cleat wiring
  2. Concealed PVC conduit wiring
  3. Wooden casing and capping
  4. Lead-sheathed wiring
Show answer & solution

Answer: (B) Concealed PVC conduit wiring

Conduits protect cables and allow rewiring.

Question 2

What is the IEC colour of the phase (line) conductor in single-phase installations?

  1. Blue
  2. Brown
  3. White
  4. Green and yellow
Show answer & solution

Answer: (B) Brown

Older installations may use red.

Question 3

What is the IEC colour of the neutral conductor?

  1. Brown
  2. Red
  3. Blue
  4. Green and yellow
Show answer & solution

Answer: (C) Blue

Older installations may use black.

Question 4

What is the colour of the protective earth conductor under IEC standards?

  1. Blue
  2. Black
  3. Brown
  4. Green and yellow
Show answer & solution

Answer: (D) Green and yellow

Earth conductors must never be used for other purposes.

Question 5

What cable size is typically used for domestic lighting circuits?

  1. 0.5 mm²
  2. 1.5 mm²
  3. 10 mm²
  4. 25 mm²
Show answer & solution

Answer: (B) 1.5 mm²

Socket circuits commonly use 2.5 mm² or larger.

Question 6

What cable size is typically used for domestic socket outlet circuits?

  1. 0.75 mm²
  2. 1 mm²
  3. 2.5 mm²
  4. 50 mm²
Show answer & solution

Answer: (C) 2.5 mm²

Air conditioners and water heaters may need 4 mm² or more.

Question 7

In which conductor must a single-pole switch be connected?

  1. The phase (line) conductor
  2. The neutral conductor
  3. The earth conductor
  4. Any conductor
Show answer & solution

Answer: (A) The phase (line) conductor

Switching the neutral would leave the appliance live when off.

Question 8

Which switching arrangement allows a staircase light to be controlled from two places?

  1. Two two-way switches
  2. A fuse and a switch
  3. One intermediate switch only
  4. Two one-way switches in series
Show answer & solution

Answer: (A) Two two-way switches

Intermediate switches are added for three or more positions.

Question 9

Which switch is added between two two-way switches to control a light from three positions?

  1. Dimmer only
  2. One-way switch
  3. Isolator
  4. Intermediate switch
Show answer & solution

Answer: (D) Intermediate switch

It reverses the connections between the two travelling wires.

Question 10

What is the maximum operating temperature of PVC-insulated cables?

  1. About 30 °C
  2. About 70 °C
  3. About 150 °C
  4. About 250 °C
Show answer & solution

Answer: (B) About 70 °C

XLPE-insulated cables can operate at about 90 °C.

Question 11

Why must cable current ratings be derated when cables are grouped together or run in hot areas?

  1. Grouping increases capacity
  2. It reduces resistance
  3. It increases insulation strength
  4. Heat dissipation is reduced, so conductors could overheat at full rated current
Show answer & solution

Answer: (D) Heat dissipation is reduced, so conductors could overheat at full rated current

Derating factors are given in installation standards.

Question 12

What type of cable is commonly used for underground LV and MV power circuits?

  1. Steel wire armoured (SWA) cable
  2. Flexible lamp cord
  3. Unarmoured flat twin cable
  4. Coaxial cable
Show answer & solution

Answer: (A) Steel wire armoured (SWA) cable

The armour gives mechanical protection.

Question 13

What is the maximum voltage drop commonly recommended for LV final circuits under IEC 60364?

  1. About 50%
  2. About 20%
  3. About 3% for lighting and 5% for other uses
  4. No limit
Show answer & solution

Answer: (C) About 3% for lighting and 5% for other uses

Excessive drop causes poor equipment performance.

Question 14

What is the voltage drop in a 20 m single-phase circuit carrying 10 A with a conductor resistance of 0.01 Ω/m (each conductor)?

  1. 0.2 V
  2. 2 V
  3. 4 V
  4. 20 V
Show answer & solution

Answer: (C) 4 V

Total resistance = 2 × 20 × 0.01 = 0.4 Ω; drop = 10 × 0.4.

Question 15

What is a distribution board (DB)?

  1. A meter only
  2. An enclosure housing the main switch, circuit breakers and RCDs that feed final circuits
  3. A transformer
  4. A generator
Show answer & solution

Answer: (B) An enclosure housing the main switch, circuit breakers and RCDs that feed final circuits

Each final circuit has its own protective device.

Question 16

What is the minimum insulation resistance generally required for LV circuits tested at 500 V DC?

  1. At least 1 kΩ
  2. Zero
  3. At least 1 Ω
  4. At least 1 MΩ
Show answer & solution

Answer: (D) At least 1 MΩ

Low values indicate damaged or damp insulation.

Question 17

Which test confirms that switches and fuses are connected in the phase conductor?

  1. Polarity test
  2. Load test
  3. Insulation resistance test
  4. Earth electrode test
Show answer & solution

Answer: (A) Polarity test

Wrong polarity leaves equipment live when switched off.

Question 18

What is earth fault loop impedance testing used for?

  1. Measuring illuminance
  2. Checking that fault current will be high enough to operate protective devices quickly
  3. Measuring frequency
  4. Measuring insulation only
Show answer & solution

Answer: (B) Checking that fault current will be high enough to operate protective devices quickly

The loop includes the phase conductor, earth path and source.

Question 19

Which rules, originally framed under the Electricity Act 1910, set safety requirements for electrical installations in Pakistan?

  1. Mines Act, 1923
  2. Explosives Act, 1884
  3. Electricity Rules, 1937
  4. PECA, 2016
Show answer & solution

Answer: (C) Electricity Rules, 1937

They cover clearances, earthing and inspection of installations.

Question 20

Why are three-pin sockets used for appliances with metal bodies?

  1. To increase current
  2. To reduce cost
  3. To increase voltage
  4. The third pin connects the appliance body to earth for safety
Show answer & solution

Answer: (D) The third pin connects the appliance body to earth for safety

A fault to the body then trips the protective device.

Question 21

What is a radial circuit?

  1. A final circuit that runs from the distribution board to outlets and ends at the last point
  2. A three-phase circuit only
  3. A DC circuit
  4. A circuit that returns to the board
Show answer & solution

Answer: (A) A final circuit that runs from the distribution board to outlets and ends at the last point

Ring circuits return to the board, allowing two paths.

Question 22

What is trunking in electrical installations?

  1. An enclosed channel, often metal or PVC, for carrying several cables
  2. A cable lug
  3. A type of switch
  4. A fuse
Show answer & solution

Answer: (A) An enclosed channel, often metal or PVC, for carrying several cables

It is used in offices and industrial buildings.

Question 23

Why should aluminium and copper conductors not be connected directly together?

  1. They are always the same
  2. Galvanic corrosion at the joint increases resistance and heating
  3. It improves conductivity
  4. It reduces cost only
Show answer & solution

Answer: (B) Galvanic corrosion at the joint increases resistance and heating

Bimetallic connectors are used.

Question 24

Which connection method is recommended for terminating large cables at switchgear?

  1. Twisting wires together
  2. Using tape only
  3. Soldering without support
  4. Crimped cable lugs bolted to terminals
Show answer & solution

Answer: (D) Crimped cable lugs bolted to terminals

Proper crimping ensures low-resistance joints.

Question 25

Why must a separate circuit be provided for high-power appliances such as air conditioners?

  1. To save cable
  2. To avoid earthing
  3. To avoid overloading general circuits and allow correctly rated protection
  4. To increase voltage
Show answer & solution

Answer: (C) To avoid overloading general circuits and allow correctly rated protection

Each high-load appliance needs a suitable cable and breaker.

Question 26

Why is the earth continuity conductor tested in new installations?

  1. To confirm a low-resistance path from exposed metal parts to the main earthing terminal
  2. To test lamps
  3. To check tariffs
  4. To measure voltage
Show answer & solution

Answer: (A) To confirm a low-resistance path from exposed metal parts to the main earthing terminal

A broken earth leaves metal parts dangerous during faults.

Question 27

What is the main advantage of conduit wiring over surface cleat wiring?

  1. Lower cost always
  2. Less safety
  3. Better mechanical protection, neater appearance and easy rewiring
  4. Faster installation always
Show answer & solution

Answer: (C) Better mechanical protection, neater appearance and easy rewiring

Steel conduit also provides extra earthing and fire protection.

Question 28

What is the purpose of a main switch at the consumer's distribution board?

  1. To increase voltage
  2. To isolate the entire installation from the supply
  3. To protect against lightning only
  4. To measure energy
Show answer & solution

Answer: (B) To isolate the entire installation from the supply

It is usually a double-pole switch or breaker.

Question 29

What is the purpose of an earth electrode in a domestic installation?

  1. To connect the installation's earthing system to the general mass of earth
  2. To supply power
  3. To measure energy
  4. To carry neutral current
Show answer & solution

Answer: (A) To connect the installation's earthing system to the general mass of earth

Pipe or rod electrodes are common.

Practice these 29 questions interactively →