Which relay measures the apparent impedance between its location and a transmission line fault?
Show answer & solution
Answer: (A) Distance relay
It compares the voltage and current at the relay point.
Electrical Engineering · Power System Protection
37 questions, each with the answer and a worked solution.
Practice interactively and track your score →Which relay measures the apparent impedance between its location and a transmission line fault?
Answer: (A) Distance relay
It compares the voltage and current at the relay point.
Which distance relay characteristic is inherently directional?
Answer: (A) Mho relay
Its circle passes through the origin of the R–X diagram.
Which distance relay is least affected by arc resistance and suits short lines?
Answer: (B) Reactance relay
It measures only the reactive component of impedance.
What portion of the protected line is usually covered by zone 1 of a distance relay?
Answer: (C) About 80 to 90%, with instantaneous tripping
Zone 1 is set short of the remote end to avoid overreach.
What is the purpose of zone 2 in distance protection?
Answer: (D) To cover the rest of the line and part of the next line with a time delay
Zone 2 is typically set to about 120% of the line.
What is the purpose of zone 3 in distance protection?
Answer: (A) To provide backup protection for adjacent lines with a longer time delay
Zone 3 must be set carefully to avoid tripping on load or power swings.
What is the primary purpose of power-swing blocking in a distance protection scheme?
Answer: (C) To prevent unwanted line tripping during stable power swings
Power swings can make the measured impedance enter relay zones without a fault.
On which principle does a differential relay operate?
Answer: (D) It compares currents entering and leaving the protected zone and operates on their difference
Merz–Price circulating current schemes use this principle.
What is a biased (percentage) differential relay?
Answer: (B) A differential relay whose operating current must exceed a percentage of the through current
Bias prevents mal-operation from CT mismatch during heavy through faults.
What does a directional overcurrent relay need besides current to determine fault direction?
Answer: (A) A polarising voltage
It is used in ring mains and parallel feeders.
On which principle does an induction disc relay operate?
Answer: (B) Torque on a metal disc produced by interacting eddy currents from two alternating fluxes
It is the basis of electromechanical IDMT relays.
What is an attracted armature relay?
Answer: (D) A relay in which an electromagnet attracts an iron armature to close contacts
It is fast and used for instantaneous protection.
Which relay protects a generator against motoring when its prime mover fails?
Answer: (C) Reverse power relay
Motoring can damage steam turbines.
Which relay protects a generator against unbalanced loading that overheats the rotor?
Answer: (A) Negative-sequence relay
Unbalanced currents induce double-frequency rotor currents.
What does an under-frequency relay do in a power system?
Answer: (B) It disconnects selected loads when frequency falls below set values
It is used for automatic load shedding.
What does a check synchronising relay ensure before closing a breaker?
Answer: (C) Voltage, frequency and phase angle are within limits on both sides
ANSI device 25 is the synchronism check relay.
What does an auto-reclosing relay do?
Answer: (D) It automatically recloses a breaker after a set dead time following a trip
Most overhead line faults are transient.
What is the function of a lockout relay (ANSI 86)?
Answer: (A) To trip breakers and prevent reclosing until reset manually
It is used for faults where reclosing would be dangerous, such as transformer faults.
Which relay responds to the heating effect of current to protect against overloads?
Answer: (B) Thermal relay
Thermal relays model the temperature rise of the protected equipment.
What is an earth fault relay?
Answer: (D) A relay that responds to residual (zero-sequence) current flowing to earth
Residual current is obtained from three CTs connected in parallel or a core-balance CT.
What is a core-balance CT used for?
Answer: (C) Sensitive earth fault detection by passing all phase conductors through one CT
Under normal balanced conditions the net flux is zero.
What is carrier (teleprotection) aided distance protection?
Answer: (D) A scheme using communication between line ends to clear end-zone faults instantaneously
Permissive and blocking schemes are common.
What is pilot-wire protection?
Answer: (C) A differential scheme for short lines using wires to compare currents at both ends
Modern schemes use fibre optic communication instead.
What is the main advantage of static relays over electromechanical relays?
Answer: (A) Low burden, fast operation and no moving parts
Static relays use electronic circuits.
Which relay protects against over-fluxing of transformers and generators?
Answer: (B) Volts-per-hertz relay
Over-excitation occurs when V/f exceeds limits.
What is the function of a breaker failure protection (ANSI 50BF)?
Answer: (C) To trip adjacent breakers if the main breaker fails to clear a fault
It provides fast local backup.
What is meant by relay overreach?
Answer: (D) Operation of a relay for faults beyond its intended reach
Underreach is the opposite.
Why is a directional earth fault relay used in parallel feeders or ring mains?
Answer: (A) To trip only the feeder carrying fault current in the fault direction
Without direction, healthy feeders might trip.
Which relay is used to detect loss of excitation in a generator?
Answer: (B) Loss-of-field (offset mho) relay
Loss of excitation makes the generator draw reactive power from the system.
What does the ANSI device number 21 represent?
Answer: (B) Distance relay
Distance relays protect transmission lines.
What does the ANSI device number 67 represent?
Answer: (C) Directional overcurrent relay
It operates only for faults in a chosen direction.
What does the ANSI device number 81 represent?
Answer: (D) Frequency relay
Under- and over-frequency elements are designated 81U and 81O.
What does the ANSI device number 79 represent?
Answer: (A) Auto-reclosing relay
Reclosers are used on overhead lines.
Why is an offset mho characteristic sometimes used in zone 3 of distance relays?
Answer: (B) To cover close-in faults behind the relay and provide reliable backup
The circle is shifted to include the origin.
What is a permissive overreach transfer trip (POTT) scheme?
Answer: (A) A scheme where an overreaching zone trips only when a permissive signal is received from the remote end
It gives fast tripping for faults anywhere on the line.
Which relay gives almost instantaneous operation independent of fault current magnitude above its setting?
Answer: (C) Instantaneous overcurrent relay
Instantaneous elements are set above the maximum through-fault current.
What is the main limitation of a plain impedance relay?
Answer: (D) It is non-directional and needs a separate directional element
Its characteristic is a circle centred on the origin.