What is the main purpose of equipment (body) earthing?
Show answer & solution
Answer: (A) To keep exposed metal parts at earth potential and protect people from electric shock
Earth faults then cause protective devices to operate.
Electrical Engineering · Power System Protection
37 questions, each with the answer and a worked solution.
Practice interactively and track your score →What is the main purpose of equipment (body) earthing?
Answer: (A) To keep exposed metal parts at earth potential and protect people from electric shock
Earth faults then cause protective devices to operate.
What is the difference between system earthing and equipment earthing?
Answer: (C) System earthing connects the neutral to earth; equipment earthing connects non-current-carrying metal parts to earth
Both are needed for safety and correct protection.
Why should the earth resistance of a large substation be very low?
Answer: (B) To keep step and touch voltages safe and allow fault currents to operate protection
Large substations aim for about 1 Ω or less.
Which method is commonly used to measure earth electrode resistance?
Answer: (A) Three-point fall-of-potential method with an earth tester
Current and potential spikes are driven into the soil at set distances.
Why are charcoal and salt sometimes placed around earth electrodes?
Answer: (D) To reduce soil resistivity and keep the surrounding soil moist
Modern practice uses earth enhancement compounds.
What is step potential?
Answer: (A) The voltage between a person's feet spaced about one metre apart during an earth fault
Substation earthing grids are designed to limit step potential.
What is touch potential?
Answer: (B) The voltage between an earthed metal structure touched by a person and the ground where the person stands
Touch potential limits are usually stricter than step potential.
What is the purpose of an earthing grid (mesh) in a substation?
Answer: (D) To provide a low-resistance path for fault current and limit step and touch potentials
Grid conductors are buried and bonded to all equipment.
Which type of surge arrester is most widely used today?
Answer: (C) Metal oxide (zinc oxide) gapless arrester
ZnO blocks have a highly non-linear resistance.
Where should a surge arrester be installed to best protect a transformer?
Answer: (D) As close as possible to the transformer terminals
Lead length reduces protection margin.
What is the basic insulation level (BIL) of equipment?
Answer: (C) The lightning impulse voltage that the insulation can withstand
BIL is used in insulation coordination.
What is insulation coordination?
Answer: (A) Matching equipment insulation strength with the protective levels of surge arresters and system overvoltages
It ensures arresters operate before insulation fails.
What are the main causes of overvoltages in power systems?
Answer: (B) Lightning strikes and switching operations
Temporary overvoltages also occur during faults and load rejection.
What is a direct lightning stroke?
Answer: (C) A lightning discharge that strikes a line or equipment directly
Shield wires intercept most direct strokes.
What is an induced lightning surge?
Answer: (A) A voltage induced on a line by a nearby lightning discharge
Induced surges mainly affect lower-voltage lines.
What is a rod gap?
Answer: (B) A simple surge protection device consisting of two rods with an air gap across an insulator
It is crude and may cause a short circuit after sparkover.
What is a horn gap arrester?
Answer: (D) An arrester with horn-shaped electrodes where the arc rises and lengthens until it is extinguished
Horn gaps were used on older distribution systems.
What happens when a travelling wave reaches an open-circuited line end?
Answer: (C) The voltage doubles due to reflection
At a short-circuited end, the voltage becomes zero and current doubles.
In the TN-S earthing system, how are the neutral and protective earth conductors arranged?
Answer: (A) Separate neutral and protective earth conductors throughout the system
TN-C-S combines them in part of the system.
In the TT earthing system, how are consumer exposed metal parts earthed?
Answer: (D) To a local earth electrode independent of the supply earth
RCDs are essential in TT systems.
Which earthing system keeps the supply isolated from earth or earthed through a high impedance?
Answer: (B) IT system
IT systems allow continued operation after a first earth fault in hospitals and process plants.
What is the function of a lightning conductor (air terminal) on a building?
Answer: (B) To intercept lightning and conduct it safely to earth
It is connected by down conductors to an earth termination.
Why are surge arresters connected between line and earth rather than in series?
Answer: (A) They must conduct only during surges and divert them to earth
Normally an arrester draws only a tiny leakage current.
What is the rated voltage of a surge arrester chosen in relation to?
Answer: (C) The maximum temporary power-frequency overvoltage at its location
Choosing too low a rating causes arrester failure.
What is a pipe earth electrode?
Answer: (D) A galvanised iron pipe buried vertically in the ground as an earth electrode
Plate, rod and pipe electrodes are common.
Why should earth resistance be checked regularly, especially in dry seasons?
Answer: (A) Soil resistivity rises when soil dries, increasing earth resistance
Many parts of Balochistan and Sindh have dry, high-resistivity soils.
What is the purpose of bonding in electrical installations?
Answer: (D) Connecting metal parts together to keep them at the same potential
Bonding reduces dangerous touch voltages.
What is the function of a surge absorber?
Answer: (B) To reduce the steepness and amplitude of incoming surges
It protects windings from steep-fronted waves.
Which value is the usual target for the resistance of earth electrodes in small distribution substations?
Answer: (C) A few ohms or less
Lower resistance improves protection operation and safety.
What is the purpose of a neutral earthing resistor (NER)?
Answer: (D) To limit earth fault current in a resistance-earthed system
NERs are common in industrial and generator neutrals.
Why are surge arresters placed at both ends of an underground cable connected to an overhead line?
Answer: (A) Surges are reflected and can double at cable terminations
Cable insulation is costly to repair.
What is the main advantage of metal oxide arresters over gapped silicon carbide arresters?
Answer: (B) No series gaps are needed and protective performance is better
ZnO blocks conduct only at high voltages.
What is the purpose of the earth termination system in lightning protection?
Answer: (D) To disperse lightning current safely into the ground
Low impedance earthing reduces dangerous potentials.
What is a counterpoise in transmission line earthing?
Answer: (A) Buried wires laid from tower footings to reduce tower footing resistance
Low footing resistance reduces back-flashover from lightning.
What is back-flashover on a transmission line?
Answer: (C) Flashover from the tower or earth wire to a phase conductor after lightning strikes the tower
High tower footing resistance raises its likelihood.
What is a lightning arrester discharge counter used for?
Answer: (C) Recording the number of arrester operations
It helps monitor arrester condition.
Which value of earth resistance is generally recommended for domestic earthing electrodes?
Answer: (B) As low as possible, commonly below about 5 Ω
Lower resistance allows protective devices to operate quickly.