On what principle does a fuse protect a circuit?
Show answer & solution
Answer: (C) A fuse element melts when excessive current flows and opens the circuit
It is the simplest overcurrent protective device.
Electrical Engineering · Power System Protection
33 questions, each with the answer and a worked solution.
Practice interactively and track your score →On what principle does a fuse protect a circuit?
Answer: (C) A fuse element melts when excessive current flows and opens the circuit
It is the simplest overcurrent protective device.
What is the purpose of silica sand filling in an HRC fuse?
Answer: (D) To absorb arc energy and quench the arc quickly
HRC fuses have high rupturing capacity.
What is the fusing factor of a fuse?
Answer: (B) Minimum fusing current divided by current rating
The fusing factor is always greater than one.
What is the cut-off current of a current-limiting fuse?
Answer: (A) The peak current reached before the fuse interrupts, lower than the prospective peak
Current limitation reduces thermal and mechanical stress.
What is the main disadvantage of a rewireable (kit-kat) fuse?
Answer: (B) Unreliable operation because a wrong wire size can be fitted
Overrated wire removes protection.
What does the I²t value of a fuse represent?
Answer: (C) The let-through energy during fault interruption
It is used to coordinate fuses with equipment withstand.
Which two trip elements are combined in a miniature circuit breaker (MCB)?
Answer: (A) A thermal element for overload and a magnetic element for short circuit
Thermal trips are slow and magnetic trips are instantaneous.
What is the magnetic trip range of a Type B MCB?
Answer: (A) 3 to 5 times rated current
Type B suits resistive and domestic lighting loads.
Which MCB type suits motors and transformers with high inrush currents?
Answer: (D) Type D
Type D trips magnetically at 10–20 times rated current.
What does a residual current device (RCD) detect?
Answer: (D) An imbalance between line and neutral currents caused by leakage to earth
RCDs protect against electric shock and fire.
What rated residual operating current is used for RCDs that protect people from electric shock?
Answer: (C) 30 mA
A 30 mA RCD operates before a dangerous shock current flows for long.
Which device combines an RCD with overcurrent protection in one unit?
Answer: (B) RCBO
RCBOs protect individual circuits against both earth leakage and overcurrent.
What protects a motor against overload in a direct-on-line starter?
Answer: (A) A thermal overload relay with the contactor
The overload relay opens the contactor coil circuit.
What is the main function of a contactor?
Answer: (D) To switch circuits on and off frequently by remote or automatic control
Contactors are not designed to clear short circuits alone.
Which fuse is commonly used on 11 kV overhead lines and transformer poles in Pakistan?
Answer: (C) Drop-out (expulsion) fuse
When it blows, the fuse holder drops to show operation.
What is discrimination between two fuses in series?
Answer: (B) Only the fuse nearest the fault operates
A rating ratio of about 2:1 often ensures discrimination.
Why is an MCB preferred over a rewireable fuse in modern installations?
Answer: (D) It can be reset, trips reliably and gives both overload and short-circuit protection
MCBs also act as switches.
What is the purpose of a surge protective device (SPD) in a low-voltage installation?
Answer: (A) To divert transient overvoltages from lightning or switching to earth
SPDs protect sensitive electronics.
What is an earth leakage circuit breaker (ELCB)?
Answer: (C) A device that disconnects supply when earth leakage current exceeds a set value
Voltage-operated ELCBs have been replaced by current-operated RCDs.
Why should the neutral not be fused separately in a single-phase circuit?
Answer: (B) If the neutral fuse blows, the circuit stays live through the phase conductor
Only the phase conductor should be protected by a single-pole device.
What is the breaking capacity rating of a domestic MCB typically?
Answer: (B) 6 kA or 10 kA
It must exceed the prospective fault current at its location.
What is single-phasing protection for three-phase motors?
Answer: (C) Protection that trips the motor when one supply phase is lost
A motor running on two phases overheats quickly.
What does an under-voltage release in a motor starter do?
Answer: (A) It disconnects the motor when supply voltage falls too low
It prevents automatic restart when supply returns.
What does the time–current characteristic of a fuse show?
Answer: (D) The time taken for the fuse to operate at different currents
Higher currents give shorter operating times.
What is a semiconductor (high-speed) fuse used for?
Answer: (A) Protecting thyristors, diodes and other power electronic devices
They have very low I²t values.
What is the function of a load-break switch?
Answer: (A) To switch normal load currents but not fault currents
It is often combined with fuses in ring main units.
What is a fuse–switch combination?
Answer: (C) A switch that also carries fuses, providing isolation and short-circuit protection
It is common in LV distribution boards.
Why should fuses be replaced with the correct rating and type?
Answer: (C) An incorrect fuse may fail to protect cables and equipment or cause unwanted operation
Fuses are coordinated with cable ratings.
What is the main purpose of cable protection by overcurrent devices?
Answer: (B) To prevent conductor temperature exceeding safe limits under overload or fault
The device rating must not exceed cable current capacity.
Why are Type C MCBs used for commercial and light industrial circuits?
Answer: (D) They tolerate moderate inrush currents of fluorescent lighting and small motors
Type C trips magnetically at 5–10 times rated current.
What does an RCD not protect against?
Answer: (A) Overloads and short circuits between line and neutral that have no earth leakage
It must be combined with overcurrent protection.
What is the purpose of the test button on an RCD?
Answer: (A) To check that the tripping mechanism works by creating a small imbalance
RCDs should be tested regularly.
What protection is provided by a motor protection circuit breaker (MPCB)?
Answer: (D) Combined overload, short-circuit and phase-loss protection for motors
MPCBs replace separate fuses and overload relays.