Power System Protection: Circuit Breakers

Electrical Engineering · Power System Protection

36 questions, each with the answer and a worked solution.

Practice interactively and track your score →
Question 1

What is the main function of a circuit breaker?

  1. To measure energy
  2. To store charge
  3. To make, carry and break normal and fault currents
  4. To regulate voltage
Show answer & solution

Answer: (C) To make, carry and break normal and fault currents

Breakers are operated by relays during faults.

Question 2

What is the main difference between a circuit breaker and an isolator?

  1. A breaker can interrupt load and fault current; an isolator is operated only with no load current
  2. An isolator interrupts fault current
  3. A breaker cannot be operated by relays
  4. They are identical
Show answer & solution

Answer: (A) A breaker can interrupt load and fault current; an isolator is operated only with no load current

Isolators provide visible isolation for maintenance.

Question 3

Which arc extinction method is used in AC circuit breakers?

  1. High resistance only
  2. Current zero interruption, preventing the arc from re-striking after a natural current zero
  3. Increasing current
  4. Reversing polarity
Show answer & solution

Answer: (B) Current zero interruption, preventing the arc from re-striking after a natural current zero

AC current passes through zero twice each cycle.

Question 4

What is restriking voltage?

  1. The normal system voltage
  2. The voltage of the battery
  3. The fault voltage before the arc
  4. The transient voltage that appears across breaker contacts immediately after arc extinction
Show answer & solution

Answer: (D) The transient voltage that appears across breaker contacts immediately after arc extinction

It may cause the arc to restrike.

Question 5

What is recovery voltage?

  1. The voltage during the arc
  2. The voltage at zero current only
  3. The normal frequency voltage that appears across breaker contacts after the transient dies out
  4. The DC voltage
Show answer & solution

Answer: (C) The normal frequency voltage that appears across breaker contacts after the transient dies out

It equals the system voltage at the breaker.

Question 6

What does RRRV stand for in circuit breaker theory?

  1. Rated reactive recovery voltage
  2. Rated rupture resistance voltage
  3. Relay reset recovery value
  4. Rate of rise of restriking voltage
Show answer & solution

Answer: (D) Rate of rise of restriking voltage

A high RRRV makes interruption more difficult.

Question 7

What is current chopping?

  1. Forced interruption of a small current before its natural zero, causing overvoltages
  2. Normal current zero interruption
  3. Arc re-striking
  4. Fault current increase
Show answer & solution

Answer: (A) Forced interruption of a small current before its natural zero, causing overvoltages

It occurs with vacuum and air-blast breakers interrupting small inductive currents.

Question 8

Which property makes SF₆ gas an excellent arc-quenching medium?

  1. It has low dielectric strength
  2. It is highly electronegative and has high dielectric strength
  3. It is flammable
  4. It is a good conductor
Show answer & solution

Answer: (B) It is highly electronegative and has high dielectric strength

Its dielectric strength is about 2.5 times that of air at atmospheric pressure.

Question 9

What is an environmental concern with SF₆ circuit breakers?

  1. It is radioactive
  2. SF₆ is a very powerful greenhouse gas
  3. It destroys copper
  4. It makes the breaker flammable
Show answer & solution

Answer: (B) SF₆ is a very powerful greenhouse gas

Leakage must be minimised and gas recovered.

Question 10

Which circuit breaker type is most widely used for medium voltages up to about 33 kV?

  1. Bulk oil breaker
  2. Air-blast breaker
  3. SF₆ only for 500 kV
  4. Vacuum circuit breaker
Show answer & solution

Answer: (D) Vacuum circuit breaker

Vacuum breakers need little maintenance.

Question 11

Why do vacuum circuit breakers need very small contact gaps?

  1. Vacuum has very high dielectric strength and rapid dielectric recovery
  2. Vacuum conducts electricity
  3. Vacuum has no insulation
  4. Vacuum is flammable
Show answer & solution

Answer: (A) Vacuum has very high dielectric strength and rapid dielectric recovery

Arc is maintained only by metal vapour from contacts.

Question 12

Which gas is produced by arcing in an oil circuit breaker and helps extinguish the arc?

  1. Nitrogen
  2. Oxygen
  3. Hydrogen
  4. Carbon dioxide
Show answer & solution

Answer: (C) Hydrogen

Hydrogen has high thermal conductivity and cools the arc.

Question 13

What is the main disadvantage of bulk oil circuit breakers?

  1. Inability to interrupt current
  2. Fire risk and large oil quantity requiring maintenance
  3. Very high cost of SF₆
  4. Very small size
Show answer & solution

Answer: (B) Fire risk and large oil quantity requiring maintenance

Minimum oil breakers reduced oil volume.

Question 14

What is the breaking capacity of a circuit breaker?

  1. The voltage rating only
  2. The operating time
  3. The normal load current
  4. The maximum fault current it can interrupt at rated voltage
Show answer & solution

Answer: (D) The maximum fault current it can interrupt at rated voltage

Breaking capacity is expressed in kA or MVA.

Question 15

What is the making capacity of a circuit breaker?

  1. The normal load current
  2. The breaking current
  3. The peak current it can safely close onto
  4. The rated voltage
Show answer & solution

Answer: (C) The peak current it can safely close onto

Making capacity is about 2.55 times rated symmetrical breaking current.

Question 16

What is the short-time current rating of a circuit breaker?

  1. The current it can carry for a specified short time, such as 1 or 3 seconds, without damage
  2. The breaking current
  3. The voltage for one second
  4. The load current for one hour
Show answer & solution

Answer: (A) The current it can carry for a specified short time, such as 1 or 3 seconds, without damage

It ensures the breaker survives while other protection clears the fault.

Question 17

What is the main advantage of gas-insulated switchgear (GIS)?

  1. Lowest cost in all cases
  2. Easy visual inspection of parts
  3. Very compact size and high reliability, suitable for cities and polluted areas
  4. No need for gas
Show answer & solution

Answer: (C) Very compact size and high reliability, suitable for cities and polluted areas

GIS uses SF₆ in sealed metal enclosures.

Question 18

Why is interlocking provided between isolators, earthing switches and circuit breakers?

  1. To reduce cost
  2. To measure current
  3. To increase speed
  4. To prevent unsafe switching sequences such as opening an isolator on load
Show answer & solution

Answer: (D) To prevent unsafe switching sequences such as opening an isolator on load

Interlocks protect personnel and equipment.

Question 19

Which operating mechanism stores energy in springs to close and open a breaker?

  1. Manual lever only
  2. Spring-operated mechanism
  3. Solenoid without springs
  4. Pneumatic mechanism only
Show answer & solution

Answer: (B) Spring-operated mechanism

Spring charging motors recharge after each operation.

Question 20

What is resistance switching in circuit breakers?

  1. Connecting a resistor across the contacts to damp restriking voltage transients
  2. Using resistance to measure current
  3. Adding resistance to the load
  4. Removing resistance
Show answer & solution

Answer: (A) Connecting a resistor across the contacts to damp restriking voltage transients

It reduces RRRV and overvoltages.

Question 21

What is an air circuit breaker (ACB) mainly used for?

  1. EHV transmission
  2. Low-voltage main distribution and large LV feeders
  3. Small domestic circuits only
  4. Battery charging
Show answer & solution

Answer: (B) Low-voltage main distribution and large LV feeders

ACBs are used up to several thousand amperes at 400 V.

Question 22

What is a moulded case circuit breaker (MCCB)?

  1. A high-voltage SF₆ breaker
  2. A fuse
  3. A contactor
  4. A low-voltage breaker in an insulated case with adjustable thermal and magnetic trips
Show answer & solution

Answer: (D) A low-voltage breaker in an insulated case with adjustable thermal and magnetic trips

MCCBs cover ratings from about 16 A to over 1,600 A.

Question 23

What is the purpose of an earthing switch in a substation?

  1. To earth isolated equipment for safe maintenance
  2. To measure earth resistance
  3. To supply loads
  4. To interrupt fault current
Show answer & solution

Answer: (A) To earth isolated equipment for safe maintenance

Earthing switches discharge trapped charge.

Question 24

What is the high-resistance method of arc interruption mainly used in?

  1. Oil breakers only
  2. EHV SF₆ breakers
  3. DC and low-voltage breakers
  4. Vacuum breakers only
Show answer & solution

Answer: (C) DC and low-voltage breakers

Arc resistance is increased by lengthening, cooling and splitting the arc.

Question 25

What is the function of arc chutes in low-voltage breakers?

  1. To store gas
  2. To measure current
  3. To close contacts
  4. To lengthen, cool and split the arc so that it is extinguished
Show answer & solution

Answer: (D) To lengthen, cool and split the arc so that it is extinguished

Arc chutes contain metal splitter plates.

Question 26

What is the rated normal current of a circuit breaker?

  1. The fault current
  2. The RMS current it can carry continuously without exceeding temperature limits
  3. The breaking current
  4. The making current
Show answer & solution

Answer: (B) The RMS current it can carry continuously without exceeding temperature limits

It is chosen above the maximum load current.

Question 27

Why are circuit breakers tested for contact resistance?

  1. High contact resistance causes heating and possible failure
  2. To measure insulation
  3. To find RRRV
  4. To check the gas pressure
Show answer & solution

Answer: (A) High contact resistance causes heating and possible failure

A micro-ohmmeter is used for the test.

Question 28

What is the dielectric medium in an air-blast circuit breaker?

  1. Oil
  2. SF₆
  3. Compressed air
  4. Vacuum
Show answer & solution

Answer: (C) Compressed air

A high-pressure air blast cools and removes the arc products.

Question 29

What is the dead time in auto-reclosing?

  1. The breaker closing time only
  2. The total fault duration
  3. The time the relay is reset
  4. The time between breaker opening and reclosing, allowing the fault arc to de-ionise
Show answer & solution

Answer: (D) The time between breaker opening and reclosing, allowing the fault arc to de-ionise

Dead times are typically a fraction of a second on transmission lines.

Question 30

What is single-pole auto-reclosing?

  1. Using fuses
  2. Tripping all three phases
  3. Tripping and reclosing only the faulted phase for single line-to-ground faults
  4. Reclosing without tripping
Show answer & solution

Answer: (C) Tripping and reclosing only the faulted phase for single line-to-ground faults

It helps maintain power transfer and stability.

Question 31

Why must the SF₆ gas pressure in breakers be monitored?

  1. To increase pressure always
  2. To cool the room
  3. Low pressure reduces insulation and breaking ability, so the breaker is blocked or alarmed
  4. To measure current
Show answer & solution

Answer: (C) Low pressure reduces insulation and breaking ability, so the breaker is blocked or alarmed

Density monitors give alarms and lockouts.

Question 32

What is the main reason vacuum breakers need little maintenance?

  1. They never operate
  2. Contacts are sealed in a vacuum interrupter and wear slowly
  3. They use oil
  4. They have no contacts
Show answer & solution

Answer: (B) Contacts are sealed in a vacuum interrupter and wear slowly

Interrupters typically last tens of thousands of operations.

Question 33

What is a disconnector (isolator) used for?

  1. Providing visible isolation of equipment for maintenance after the breaker opens
  2. Breaking fault current
  3. Improving power factor
  4. Measuring voltage
Show answer & solution

Answer: (A) Providing visible isolation of equipment for maintenance after the breaker opens

Isolators are operated off-load.

Question 34

What is meant by the operating time of a circuit breaker?

  1. The time between maintenance
  2. The time to close the breaker
  3. The life of the breaker
  4. The time from receiving a trip signal to final arc extinction
Show answer & solution

Answer: (D) The time from receiving a trip signal to final arc extinction

EHV breakers operate in about two to three cycles.

Question 35

What is a recloser in distribution systems?

  1. A capacitor
  2. A manual isolator
  3. A fuse with no reclosing
  4. A self-contained breaker with built-in control that trips and recloses automatically
Show answer & solution

Answer: (D) A self-contained breaker with built-in control that trips and recloses automatically

Reclosers clear temporary faults without long outages.

Question 36

What is a sectionaliser?

  1. A circuit breaker for high fault currents
  2. A device that counts recloser operations and opens during the dead time to isolate a faulty section
  3. A fuse
  4. A transformer
Show answer & solution

Answer: (B) A device that counts recloser operations and opens during the dead time to isolate a faulty section

It cannot interrupt fault current itself.