Question 1
What is the main purpose of a power system protection scheme?
- To measure energy for billing
- To regulate voltage continuously
- To improve power factor
- To detect faults and isolate only the faulty part quickly, keeping the rest of the system in service
Show answer & solution
Answer: (D) To detect faults and isolate only the faulty part quickly, keeping the rest of the system in service
Protection limits damage and maintains supply to healthy sections.
Question 2
Why are protection zones arranged to overlap?
- To avoid using CTs
- So that no part of the system is left unprotected
- To increase fault current
- To reduce the number of breakers
Show answer & solution
Answer: (B) So that no part of the system is left unprotected
Overlap is usually achieved around circuit breakers.
Question 3
What is selectivity (discrimination) in protection?
- The ability to trip all breakers
- The speed of the relay only
- The ability to trip only the breakers nearest the fault
- The ability to measure voltage
Show answer & solution
Answer: (C) The ability to trip only the breakers nearest the fault
Good selectivity minimises the area of supply loss.
Question 4
What is sensitivity of a protective relay?
- Its ability to detect the smallest fault conditions it is meant to detect
- Its physical size
- Its operating time
- Its cost
Show answer & solution
Answer: (A) Its ability to detect the smallest fault conditions it is meant to detect
Sensitivity is set by the minimum operating quantity.
Question 5
What is meant by stability of a protection scheme?
- It must operate for all faults anywhere
- It must ignore internal faults
- It must not operate for faults outside its zone or for normal conditions
- It must be slow
Show answer & solution
Answer: (C) It must not operate for faults outside its zone or for normal conditions
Differential schemes must remain stable for through faults.
Question 6
What is backup protection?
- Protection used only during testing
- Protection that operates if the primary protection or its breaker fails
- The main protection of a zone
- Lightning protection only
Show answer & solution
Answer: (B) Protection that operates if the primary protection or its breaker fails
Backup protection usually operates after a time delay.
Question 7
What is the function of a current transformer (CT) in protection?
- To reduce high primary current to a standard low value for relays and meters
- To supply loads
- To store energy
- To step up voltage
Show answer & solution
Answer: (A) To reduce high primary current to a standard low value for relays and meters
Standard secondary ratings are 1 A and 5 A.
Question 8
Why must the secondary of a current transformer never be left open while primary current flows?
- The CT will stop working safely
- It improves accuracy
- Current becomes zero
- A dangerously high voltage can appear across the secondary and the core may overheat
Show answer & solution
Answer: (D) A dangerously high voltage can appear across the secondary and the core may overheat
CT secondaries are shorted before disconnecting meters.
Question 9
What is the usual secondary voltage of a voltage (potential) transformer used for protection?
- 1 V
- 11 kV
- 110 V (line to line)
- 1,000 V
Show answer & solution
Answer: (C) 110 V (line to line)
Relays and meters are designed for this standard voltage.
Question 10
What does CT saturation cause in a protection scheme?
- Higher accuracy
- Distorted secondary current that may cause relays to mis-operate or operate slowly
- Higher primary current
- Lower burden
Show answer & solution
Answer: (B) Distorted secondary current that may cause relays to mis-operate or operate slowly
CTs are sized to avoid saturation during fault currents.
Question 11
What does the accuracy class designation 5P20 for a protection CT mean?
- Composite error within 5% up to 20 times rated current
- 5 A secondary and 20 kV insulation
- 5 VA burden at 20 A
- Error of 20% at 5 times current
Show answer & solution
Answer: (A) Composite error within 5% up to 20 times rated current
Protection CTs must remain accurate at high fault currents.
Question 12
What is the burden of a CT?
- The turns ratio
- The primary current
- The insulation level
- The load connected to its secondary, expressed in VA or ohms
Show answer & solution
Answer: (D) The load connected to its secondary, expressed in VA or ohms
Long leads and relays add burden.
Question 13
What is the knee-point voltage of a CT?
- The secondary voltage above which a small increase in voltage causes a large increase in exciting current
- The breakdown voltage of insulation
- The voltage at zero current
- The rated voltage of the primary
Show answer & solution
Answer: (A) The secondary voltage above which a small increase in voltage causes a large increase in exciting current
It defines the onset of saturation.
Question 14
How is the plug setting multiplier (PSM) of an overcurrent relay calculated?
- Plug setting × fault current
- Fault current ÷ (plug setting × CT ratio)
- Time setting × plug setting
- CT ratio ÷ fault current
Show answer & solution
Answer: (B) Fault current ÷ (plug setting × CT ratio)
PSM shows how many times the setting the relay current is.
Question 15
What is the PSM of a relay with 100% plug setting on a 1 A relay fed from a 400/1 CT when the fault current is 4,000 A?
- 4
- 10
- 40
- 100
Show answer & solution
Answer: (B) 10
Relay current = 4000/400 = 10 A; PSM = 10/1 = 10.
Question 16
What does the time multiplier setting (TMS) of an IDMT relay adjust?
- The current setting
- The relay voltage
- The CT ratio
- The operating time for a given PSM
Show answer & solution
Answer: (D) The operating time for a given PSM
Operating time is proportional to TMS.
Question 17
What is the IEC standard inverse characteristic equation for an IDMT relay?
- t = 13.5 × TMS/(PSM − 1)
- t = 80 × TMS/(PSM² − 1)
- t = 0.14 × TMS/(PSM^0.02 − 1)
- t = TMS × PSM
Show answer & solution
Answer: (C) t = 0.14 × TMS/(PSM^0.02 − 1)
Very inverse and extremely inverse curves use other constants.
Question 18
What is the approximate operating time of a standard inverse relay at PSM 10 and TMS 0.1?
- About 0.03 s
- About 0.3 s
- About 1.0 s
- About 3 s
Show answer & solution
Answer: (B) About 0.3 s
t = 0.14 × 0.1/(10^0.02 − 1) ≈ 0.297 s.
Question 19
What is the typical coordination (grading) time interval between successive overcurrent relays?
- About 0.01 s
- About 0.3 to 0.4 s
- About 2 s
- About 5 s
Show answer & solution
Answer: (B) About 0.3 to 0.4 s
It allows for breaker opening time, relay overshoot and errors.
Question 20
What are the three basic methods of discrimination between overcurrent relays?
- By voltage, frequency and colour
- By size, cost and weight
- By CT ratio only
- By time, by current, and by both time and current (inverse time)
Show answer & solution
Answer: (D) By time, by current, and by both time and current (inverse time)
Inverse-time grading is most common in radial systems.
Question 21
What is the difference between primary relay and auxiliary relay?
- A primary relay responds to the faulted quantity; an auxiliary relay helps the primary relay by switching circuits
- An auxiliary relay detects faults first
- They are identical
- A primary relay only gives alarms
Show answer & solution
Answer: (A) A primary relay responds to the faulted quantity; an auxiliary relay helps the primary relay by switching circuits
Trip relays and lockout relays are auxiliary relays.
Question 22
Which source normally supplies the tripping circuits of substation breakers?
- The AC load
- The CT secondary only
- A station battery (DC supply)
- The lighting circuit
Show answer & solution
Answer: (C) A station battery (DC supply)
DC supply remains available even when AC fails during faults.
Question 23
What is trip circuit supervision?
- Measuring insulation
- Measuring the fault current
- Testing relays monthly
- Continuous monitoring of the breaker trip circuit to detect open circuits or loss of supply
Show answer & solution
Answer: (D) Continuous monitoring of the breaker trip circuit to detect open circuits or loss of supply
A healthy trip circuit is essential for clearing faults.
Question 24
Why is the speed of fault clearing important in transmission systems?
- It improves power factor
- It reduces energy bills
- It limits damage and improves transient stability
- It increases fault current
Show answer & solution
Answer: (C) It limits damage and improves transient stability
EHV systems use protection operating in a few cycles.
Question 25
What is the meaning of the reach of a protection relay?
- The extent of the network over which it will operate for faults
- The operating time
- The relay weight
- The distance to the control room
Show answer & solution
Answer: (A) The extent of the network over which it will operate for faults
Distance relays have defined reaches for each zone.
Question 26
- Protection that responds only to faults within a clearly defined zone, such as differential protection
- Protection that responds to faults anywhere
- Protection by fuses only
- Protection by lightning arresters
Show answer & solution
Answer: (A) Protection that responds only to faults within a clearly defined zone, such as differential protection
Unit protection is inherently selective.
Question 27
What is non-unit protection?
- Pilot-wire protection
- Differential protection
- Protection whose zone is not sharply defined, such as overcurrent or distance protection
- Buchholz protection
Show answer & solution
Answer: (C) Protection whose zone is not sharply defined, such as overcurrent or distance protection
Selectivity is obtained by time grading or zones.
Question 28
What does the ANSI device number 50 represent?
- Time overcurrent relay
- Distance relay
- Differential relay
- Instantaneous overcurrent relay
Show answer & solution
Answer: (D) Instantaneous overcurrent relay
Device 51 is the time overcurrent relay.
Question 29
What does the ANSI device number 87 represent?
- Distance relay
- Directional overcurrent relay
- Differential protection relay
- Reclosing relay
Show answer & solution
Answer: (C) Differential protection relay
Device 21 is distance and 67 is directional overcurrent.
Question 30
What is the main advantage of numerical (microprocessor) relays?
- They need no power supply
- Multiple protection functions, self-monitoring, event recording and communication in one device
- They need no CTs
- They are purely mechanical
Show answer & solution
Answer: (B) Multiple protection functions, self-monitoring, event recording and communication in one device
Numerical relays have largely replaced electromechanical relays.
Question 31
Which international standard defines communication within substation automation systems?
- IEC 60034
- ISO 9001
- IEC 60228
- IEC 61850
Show answer & solution
Answer: (D) IEC 61850
IEC 61850 supports fast messaging between relays.
Question 32
What is the main purpose of a current transformer with a high knee-point voltage in differential protection?
- To increase burden
- To reduce accuracy
- To reduce secondary current to zero
- To avoid saturation during heavy through faults and keep the scheme stable
Show answer & solution
Answer: (D) To avoid saturation during heavy through faults and keep the scheme stable
High-impedance schemes need class PX CTs.
Question 33
What is a protection relay setting study?
- A study of load growth
- A study of tower design
- A study to choose relay pickup and time settings so that faults are cleared selectively and quickly
- A study of energy sales
Show answer & solution
Answer: (C) A study to choose relay pickup and time settings so that faults are cleared selectively and quickly
Coordination curves are plotted for upstream and downstream devices.
Question 34
What is the dependability of a protection system?
- The number of CTs
- The certainty that it will operate correctly for faults it is meant to clear
- Its size
- Its cost
Show answer & solution
Answer: (B) The certainty that it will operate correctly for faults it is meant to clear
Security is the certainty that it will not operate wrongly.
Question 35
What is the security of a protection system?
- The certainty that it will not operate incorrectly
- The speed of operation
- The size of the relay
- The sensitivity to small faults
Show answer & solution
Answer: (A) The certainty that it will not operate incorrectly
Balancing dependability and security is a key design aim.
Question 36
Why are CT secondary circuits earthed at one point?
- For safety and to provide a reference, avoiding multiple earth paths
- To open the circuit
- To increase burden
- To reduce accuracy
Show answer & solution
Answer: (A) For safety and to provide a reference, avoiding multiple earth paths
Multiple earths can cause unwanted currents.
Question 37
What is the function of a VT fuse failure supervision function in distance relays?
- To trip on lightning
- To block distance tripping when the voltage input is lost
- To start the generator
- To measure current
Show answer & solution
Answer: (B) To block distance tripping when the voltage input is lost
Loss of voltage could make a distance relay see zero impedance.