Why are transmission systems operated at high voltages?
Show answer & solution
Answer: (A) To reduce current and therefore line losses for the same power
Losses are I²R, and current falls as voltage rises.
Electrical Engineering · Power Systems
38 questions, each with the answer and a worked solution.
Practice interactively and track your score →Why are transmission systems operated at high voltages?
Answer: (A) To reduce current and therefore line losses for the same power
Losses are I²R, and current falls as voltage rises.
How do transmission line losses vary with transmission voltage for the same power and power factor?
Answer: (C) Inversely with the square of the voltage
Doubling voltage reduces losses to one quarter.
What are the highest AC transmission voltages used in Pakistan's national grid?
Answer: (C) 500 kV and 220 kV
NTDC operates the 500 kV and 220 kV grid.
What is the DC voltage of the Matiari–Lahore HVDC transmission line?
Answer: (D) ±660 kV
It is Pakistan's first HVDC line, commissioned in 2021.
What power can the Matiari–Lahore HVDC line transmit under rated conditions?
Answer: (C) 4,000 MW
It carries power from southern coal plants to load centres in the north.
Which conductor is most widely used for overhead transmission lines?
Answer: (B) ACSR (aluminium conductor steel reinforced)
The steel core gives strength and aluminium carries current.
What is skin effect?
Answer: (A) The tendency of alternating current to flow near the surface of a conductor
It increases effective AC resistance, especially at high frequency and large diameter.
What is corona in transmission lines?
Answer: (B) Ionisation of air around conductors when the electric field exceeds the air's breakdown strength
Corona produces a violet glow, hissing noise, ozone and power loss.
Which conductor arrangement can reduce corona loss on extra-high-voltage lines?
Answer: (D) Bundled conductors
Bundling increases effective diameter and reduces surface field.
How does wet weather affect corona loss?
Answer: (A) It increases corona loss
Rain and fog lower the critical disruptive voltage.
What is the Ferranti effect?
Answer: (B) A rise in receiving-end voltage above sending-end voltage on a lightly loaded long line
It is caused by line charging capacitance.
How are shunt reactors used on long EHV lines?
Answer: (D) To absorb reactive power and control overvoltages during light load
They counter the Ferranti effect.
Up to about what length is an overhead line treated as a short line, neglecting capacitance?
Answer: (B) 80 km
Medium lines (80–240 km) use nominal T or π models.
What is the relationship between the ABCD constants of a passive transmission network?
Answer: (A) AD − BC = 1
For a symmetrical network A = D.
What is the surge impedance of a lossless transmission line?
Answer: (C) √(L/C)
Typical overhead lines have surge impedances of about 400 Ω.
What is surge impedance loading (SIL)?
Answer: (D) The power delivered when a line is terminated in its surge impedance, V²/Zc
At SIL, reactive power generated and absorbed by the line balance.
What is the formula for sag of a conductor between supports at equal levels?
Answer: (B) S = wl²/(8T)
w is weight per unit length, l span and T horizontal tension.
How does an increase in conductor temperature affect sag?
Answer: (D) Sag increases
Thermal expansion lengthens the conductor.
Which type of insulator is used for overhead lines above about 33 kV?
Answer: (C) Suspension (disc) insulators
Disc strings can be extended for higher voltages.
Why is string efficiency of suspension insulators less than 100%?
Answer: (A) Voltage is not distributed equally across the discs because of shunt capacitance to earth
The disc nearest the line conductor is most stressed.
Which method improves the voltage distribution across a string of suspension insulators?
Answer: (C) Using a guard (grading) ring
The guard ring adds capacitance that equalises voltage.
What is the main purpose of the earth (shield) wire on top of transmission towers?
Answer: (A) To protect phase conductors from direct lightning strikes
It is earthed at every tower.
Why are transmission lines transposed?
Answer: (D) To balance the inductance and capacitance of the three phases
Each phase occupies each position for one-third of the length.
Which law states that the most economical conductor size is when the annual cost of energy lost equals the annual interest and depreciation on the conductor cost?
Answer: (B) Kelvin's law
It is used for choosing economic conductor cross-section.
What is a major advantage of HVDC over HVAC for long-distance bulk transmission?
Answer: (D) Lower losses and no reactive power or stability limit with distance
HVDC also links asynchronous systems.
Which HVDC link uses the earth or sea as its return path?
Answer: (C) Monopolar link
A bipolar link has positive and negative poles.
What type of HVDC link is the Matiari–Lahore line?
Answer: (A) Bipolar link
Bipolar links can operate on one pole if the other fails.
What is a back-to-back HVDC station used for?
Answer: (B) Connecting two AC systems at the same location that may have different frequencies or be unsynchronised
There is no long DC line in a back-to-back link.
Which power electronic devices are used in conventional line-commutated HVDC converters?
Answer: (A) Thyristors
Modern VSC-HVDC uses IGBTs.
Which insulation material is widely used in modern high-voltage underground cables?
Answer: (B) Cross-linked polyethylene (XLPE)
XLPE cables are lighter and need less maintenance than oil-filled cables.
Why is the charging current of underground cables much larger than that of overhead lines?
Answer: (D) Cables have much higher capacitance
This limits the length of long AC cables.
Which test is used to locate a fault in an underground cable?
Answer: (C) Murray loop test
It uses a Wheatstone bridge principle.
What is the purpose of series capacitors in long transmission lines?
Answer: (C) To reduce effective line reactance and increase power transfer capability
Series compensation improves stability.
How does using bundled conductors affect line inductance?
Answer: (D) It reduces line inductance
A larger effective radius reduces reactance and increases capacity.
What is proximity effect in conductors?
Answer: (A) Non-uniform current distribution caused by the magnetic field of nearby conductors
Like skin effect, it increases AC resistance.
Which voltage levels does NTDC use at its grid stations to supply DISCOs?
Answer: (C) 220 kV and 132 kV
DISCOs then distribute power at 11 kV and 400/230 V.
What is the main reason for using steel lattice towers for EHV lines?
Answer: (C) They are strong and light for their height and carry heavy conductors over long spans
Tower design depends on voltage, conductor and terrain.
What happens to line capacitance when the spacing between conductors increases?
Answer: (D) It decreases
Capacitance per phase varies inversely with ln(D/r).