What is steady-state stability?
Show answer & solution
Answer: (B) The ability of a system to stay in synchronism after small, gradual changes in load
It is limited by the maximum power transfer.
Electrical Engineering · Power Systems
35 questions, each with the answer and a worked solution.
Practice interactively and track your score →What is steady-state stability?
Answer: (B) The ability of a system to stay in synchronism after small, gradual changes in load
It is limited by the maximum power transfer.
What is transient stability?
Answer: (C) The ability of a system to remain in synchronism after a large sudden disturbance such as a fault
It depends on fault type, location and clearing time.
What does the swing equation describe?
Answer: (A) The motion of a generator rotor angle in response to the difference between mechanical and electrical power
M d²δ/dt² = Pm − Pe.
How is the inertia constant H of a generator defined?
Answer: (D) Stored kinetic energy at rated speed divided by the machine MVA rating
H is in MJ/MVA or seconds.
Which criterion is used to assess transient stability of a single machine connected to an infinite bus?
Answer: (A) Equal area criterion
The accelerating and decelerating areas must balance.
What is the critical clearing time?
Answer: (C) The maximum time a fault can last before the system loses stability
Faster clearing improves transient stability.
Which measure improves transient stability of a power system?
Answer: (B) Faster fault clearing with high-speed breakers and relays
Auto-reclosing and series compensation also help.
What is the maximum power that can be transferred over a lossless line between voltages V1 and V2 with reactance X?
Answer: (D) V1V2/X
Maximum transfer occurs at a power angle of 90°.
What is the purpose of a power system stabiliser (PSS)?
Answer: (B) To add damping to rotor oscillations through the excitation system
PSSs improve small-signal stability.
What is the main function of governor droop control?
Answer: (C) To share load changes among generators in proportion to their ratings and limit frequency deviation
A typical droop is about 4–5%.
What is automatic generation control (AGC)?
Answer: (A) A system that adjusts generator outputs to restore frequency and scheduled interchange
AGC is secondary frequency control.
What does system frequency fall indicate in a power system?
Answer: (D) Generation is less than load
Frequency is the indicator of real power balance.
What is under-frequency load shedding?
Answer: (A) Automatic disconnection of selected loads when frequency falls below set limits
It prevents total system collapse.
Which devices are used to control voltage in power systems?
Answer: (D) AVRs, transformer tap changers, shunt capacitors, reactors, SVCs and STATCOMs
Voltage control relies on reactive power control.
What is a STATCOM?
Answer: (C) A voltage-source converter that supplies or absorbs reactive power rapidly
It is a FACTS device for voltage support.
What does FACTS stand for in power systems?
Answer: (B) Flexible AC Transmission Systems
FACTS devices control power flow and voltage.
What is voltage collapse?
Answer: (C) A progressive uncontrollable fall in voltage due to insufficient reactive power support
It often follows heavy loading and loss of generators or lines.
What is islanding in a power system?
Answer: (B) A part of the network separating from the grid and continuing to operate on its own generation
Controlled islanding can prevent total blackout.
Which centre in Islamabad controls and dispatches Pakistan's national grid?
Answer: (A) National Power Control Centre (NPCC)
NPCC monitors and dispatches generation across the national grid.
What is SCADA used for in power systems?
Answer: (D) Remote monitoring and control of substations and networks
Supervisory Control and Data Acquisition systems support grid operation.
What is dynamic stability?
Answer: (B) The ability of a system to remain stable over a longer period with controls such as AVRs and governors acting
It considers small oscillations with control actions.
How does increasing transmission voltage affect steady-state stability limit?
Answer: (A) It increases the limit
Maximum power transfer is proportional to V1V2.
What is the main purpose of auto-reclosing on transmission lines?
Answer: (D) To restore the line quickly after transient faults
Most faults on overhead lines are temporary.
What happens to generator rotor angle during a fault close to the generator?
Answer: (C) It increases because electrical output falls while mechanical input stays nearly constant
The rotor accelerates during the fault.
What is an SVC (static VAR compensator)?
Answer: (C) A thyristor-controlled combination of reactors and capacitors that regulates reactive power
SVCs provide fast voltage support.
What is the purpose of a primary frequency response from generators?
Answer: (D) Immediate automatic change of output by governors when frequency changes
Primary response acts within seconds.
What is the typical permissible frequency range for normal operation of a 50 Hz grid?
Answer: (B) Close to 50 Hz within a small band of about ±1%
Grid codes set normal and emergency frequency bands.
What is load–frequency control?
Answer: (A) Control of generator outputs to keep frequency and tie-line power at scheduled values
It combines governor action and AGC.
Why does a large sudden loss of generation cause frequency to fall?
Answer: (D) Load exceeds generation, so rotating machines slow down as kinetic energy is drawn
System inertia slows the initial rate of fall.
How does low system inertia, as with high solar and wind penetration, affect frequency stability?
Answer: (A) Frequency changes faster after disturbances
Fast frequency response and synthetic inertia help offset low inertia.
What is a tie line in power systems?
Answer: (B) A transmission line interconnecting two control areas or systems
Power exchange over tie lines is scheduled and controlled.
What is the main cause of hunting (rotor oscillations) between interconnected generators?
Answer: (C) Sudden changes in load or system conditions with insufficient damping
Damper windings and PSSs reduce oscillations.
How does series compensation improve stability of long lines?
Answer: (B) It reduces line reactance, increasing maximum power transfer
Too much series compensation can cause subsynchronous resonance.
What is subsynchronous resonance?
Answer: (C) An oscillation between series-compensated line electrical modes and turbine-generator shaft torsional modes
It can damage turbine-generator shafts.
What is the main purpose of a grid code?
Answer: (D) To set technical rules for connecting to and operating on the transmission system
NEPRA approves the grid code in Pakistan.