On which principle does a transformer work?
Show answer & solution
Answer: (D) Mutual induction between two windings linked by a common magnetic flux
A changing flux from the primary induces an emf in the secondary.
Electrical Engineering · Electrical Machines
41 questions, each with the answer and a worked solution.
Practice interactively and track your score →On which principle does a transformer work?
Answer: (D) Mutual induction between two windings linked by a common magnetic flux
A changing flux from the primary induces an emf in the secondary.
What is the emf equation of a transformer winding?
Answer: (B) E = 4.44 f N Φm
Φm is the peak flux in the core.
What emf is induced in a 500-turn winding at 50 Hz with a peak core flux of 0.01 Wb?
Answer: (C) 1,110 V
E = 4.44 × 50 × 500 × 0.01 = 1,110 V.
Why is a transformer core made of thin laminations?
Answer: (A) To reduce eddy current loss
Insulated laminations break up eddy current paths.
Why is silicon steel used for transformer cores?
Answer: (D) It has low hysteresis loss and higher resistivity
About 3% silicon reduces core losses.
How does hysteresis loss vary according to Steinmetz's formula?
Answer: (C) In proportion to frequency and to Bm raised to about 1.6
Wh = η f Bm^1.6 V.
How does eddy current loss in a core vary with frequency?
Answer: (B) With the square of frequency
We ∝ f² Bm² t², where t is lamination thickness.
How do the copper losses of a transformer vary with load?
Answer: (A) With the square of the load current
Copper loss = I²R.
Why are the iron losses of a transformer called constant losses?
Answer: (B) They depend on voltage and frequency, which stay nearly constant, not on load
Iron loss is present whenever the transformer is energised.
When does a transformer operate at maximum efficiency?
Answer: (C) When copper loss equals iron loss
This occurs at a fraction √(Pi/Pcu,fl) of full load.
What does the open-circuit test on a transformer mainly determine?
Answer: (A) Iron (core) losses and the magnetising branch parameters
It is done on the LV side with the HV side open.
What does the short-circuit test on a transformer mainly determine?
Answer: (D) Full-load copper loss and equivalent impedance
It is done on the HV side with the LV side shorted at reduced voltage.
Why is the short-circuit test normally performed on the HV side?
Answer: (A) Rated current on the HV side is lower and the required voltage is a convenient value
Only a few percent of rated voltage is needed to circulate rated current.
What is the voltage regulation of a transformer?
Answer: (B) The change in secondary voltage from no load to full load, as a percentage of full-load voltage
Low regulation is desirable.
For which transformers is all-day efficiency an important measure?
Answer: (D) Distribution transformers, which are energised all day but loaded variably
All-day efficiency is based on energy over 24 hours.
What is the turns ratio of an 11,000/400 V distribution transformer?
Answer: (C) 27.5
11,000/400 = 27.5.
How does a transformer affect the supply frequency?
Answer: (D) It does not change the frequency
Transformers change voltage and current levels only.
What happens if a transformer primary is connected to a DC supply of rated voltage?
Answer: (A) A very large current flows because there is no back emf, and the winding may burn
With steady DC, only the winding resistance limits current.
What is the main difference between core-type and shell-type transformers?
Answer: (B) In core type windings surround the core; in shell type the core surrounds the windings
Shell type gives better mechanical support against short-circuit forces.
What is the purpose of the conservator tank in an oil-filled transformer?
Answer: (C) To allow for expansion and contraction of oil and keep the main tank full
It also reduces the oil surface exposed to air.
What is the purpose of the breather with silica gel on a transformer?
Answer: (D) To remove moisture from air entering the conservator
Silica gel turns pink when saturated with moisture.
What are the two main functions of transformer oil?
Answer: (C) Insulation and cooling
Mineral oil carries heat away and insulates windings.
What does the cooling designation ONAN mean?
Answer: (A) Oil natural, air natural
ONAF adds forced air cooling by fans.
What is the purpose of an on-load tap changer?
Answer: (B) To adjust the voltage ratio without interrupting the load
Tap changers keep secondary voltage within limits as load varies.
Why are tap changers usually fitted on the HV winding?
Answer: (C) The current is lower and fine voltage steps are easier on the HV side
Lower current reduces contact wear and arcing.
What is the main advantage of an autotransformer over a two-winding transformer of the same rating?
Answer: (A) It uses less copper and has higher efficiency
A single winding is shared by primary and secondary.
What is the main disadvantage of an autotransformer?
Answer: (B) There is no electrical isolation between primary and secondary
A fault can apply the full primary voltage to the secondary side.
Which condition is essential for parallel operation of two transformers?
Answer: (D) Same voltage ratio, polarity, phase sequence and vector group
Equal per-unit impedance also ensures proper load sharing.
What does the vector group Dyn11 of a distribution transformer indicate?
Answer: (C) Delta HV, star LV with neutral, and LV leading HV by 30°
Dyn11 is widely used for 11 kV/400 V distribution transformers.
What is magnetising inrush current?
Answer: (A) A large transient current drawn when a transformer is first energised
Inrush can be many times rated current and contains second harmonics.
What is the typical no-load current of a power transformer as a percentage of rated current?
Answer: (B) About 2 to 5%
It is mainly magnetising current lagging the voltage by nearly 90°.
What causes the leakage reactance of a transformer?
Answer: (D) Flux that links only one winding and not the other
Leakage reactance limits short-circuit current.
What is the efficiency of a transformer delivering 100 kW with total losses of 2 kW?
Answer: (B) About 98%
η = 100/(100 + 2) ≈ 98%.
Why are transformers rated in kVA rather than kW?
Answer: (D) Their losses depend on voltage and current, not on the load power factor
Copper loss depends on current and iron loss on voltage.
Which test loads two identical transformers back-to-back for a heat run with little energy?
Answer: (C) Sumpner's (back-to-back) test
Only losses are supplied from the mains.
How does the efficiency of a transformer compare with that of rotating machines?
Answer: (A) It is higher because there are no moving parts and no friction losses
Large transformers reach efficiencies above 99%.
Why is the neutral of the star-connected LV winding of a distribution transformer earthed?
Answer: (A) To provide a reference for phase voltages and a path for earth fault current
Earthing allows protective devices to operate on earth faults.
What is the purpose of an impedance (per-unit) value on a transformer nameplate?
Answer: (C) To indicate short-circuit current level, voltage regulation and parallel load sharing
Higher impedance lowers fault current but increases voltage drop.
What is the effect of operating a 50 Hz transformer on a lower frequency at rated voltage?
Answer: (D) Core flux increases and the core may saturate and overheat
Flux is proportional to V/f.
What is an instrument transformer?
Answer: (A) A transformer used to step down high voltages or currents for measurement and protection
Current and voltage transformers feed meters and relays.
What happens to the copper loss of a transformer at half load compared with full load?
Answer: (C) It falls to one quarter
Copper loss is proportional to the square of load current.