Circuit Analysis: Three-Phase Circuits

Electrical Engineering · Circuit Analysis

35 questions, each with the answer and a worked solution.

Practice interactively and track your score →
Question 1

What is the phase displacement between the voltages of a balanced three-phase supply?

  1. 60°
  2. 90°
  3. 120°
  4. 180°
Show answer & solution

Answer: (C) 120°

The three phase voltages are equal in magnitude and 120° apart.

Question 2

In a balanced star connection, how is line voltage related to phase voltage?

  1. Line voltage is half the phase voltage
  2. Line voltage is √3 times the phase voltage
  3. Line voltage is three times phase voltage
  4. Line voltage equals phase voltage
Show answer & solution

Answer: (B) Line voltage is √3 times the phase voltage

Line current equals phase current in star.

Question 3

In a balanced delta connection, how is line current related to phase current?

  1. Line current is √3 times the phase current
  2. Line current is half the phase current
  3. Line current equals phase current
  4. Line current is three times the phase current
Show answer & solution

Answer: (A) Line current is √3 times the phase current

Line voltage equals phase voltage in delta.

Question 4

What is the total power in a balanced three-phase load?

  1. 3 VL IL cos φ
  2. √3 VL IL sin φ
  3. VL IL cos φ
  4. √3 VL IL cos φ
Show answer & solution

Answer: (D) √3 VL IL cos φ

VL and IL are line values.

Question 5

What is the power drawn by a balanced three-phase load at 400 V, 10 A and power factor 0.8?

  1. 3.2 kW
  2. 4.0 kW
  3. About 5.54 kW
  4. 9.6 kW
Show answer & solution

Answer: (C) About 5.54 kW

P = √3 × 400 × 10 × 0.8 ≈ 5,543 W.

Question 6

What is the phase voltage of an 11 kV star-connected system?

  1. 3.67 kV
  2. About 6.35 kV
  3. 11 kV
  4. 19 kV
Show answer & solution

Answer: (B) About 6.35 kV

Vph = 11/√3 ≈ 6.35 kV.

Question 7

What happens to the direction of rotation of a three-phase induction motor when any two supply lines are interchanged?

  1. The motor stops
  2. It reverses
  3. It stays the same
  4. The speed doubles
Show answer & solution

Answer: (B) It reverses

Interchanging two lines reverses the phase sequence.

Question 8

What is the current in the neutral of a balanced star-connected load?

  1. Zero
  2. √3 times the line current
  3. Three times the phase current
  4. Equal to the line current
Show answer & solution

Answer: (A) Zero

The three balanced phase currents add to zero.

Question 9

What is an advantage of three-phase power over single-phase power?

  1. It needs more conductor material
  2. It cannot run motors
  3. It produces pulsating torque
  4. Instantaneous power in a balanced system is constant
Show answer & solution

Answer: (D) Instantaneous power in a balanced system is constant

Constant power gives smooth torque in motors.

Question 10

How much conductor material does a three-phase three-wire system need compared with a single-phase two-wire system for the same power, distance and losses?

  1. 50%
  2. 75%
  3. 100%
  4. 150%
Show answer & solution

Answer: (B) 75%

Three-phase transmission saves about 25% of conductor material.

Question 11

In the two-wattmeter method, how is the total power of a three-phase load found?

  1. By taking the larger reading
  2. By taking the difference of the readings
  3. By adding the two wattmeter readings
  4. By multiplying the readings
Show answer & solution

Answer: (C) By adding the two wattmeter readings

P = W1 + W2 for any balanced or unbalanced three-wire load.

Question 12

In the two-wattmeter method for a balanced load, what is the power factor if both wattmeters read equal values?

  1. Unity
  2. Zero
  3. 0.866
  4. 0.5
Show answer & solution

Answer: (A) Unity

Equal readings mean φ = 0.

Question 13

In the two-wattmeter method for a balanced load, what is the power factor when one wattmeter reads zero?

  1. Unity
  2. Zero
  3. 0.707
  4. 0.5
Show answer & solution

Answer: (D) 0.5

One reading is zero when φ = 60°.

Question 14

In the two-wattmeter method, what does a negative reading on one wattmeter indicate for a balanced load?

  1. The power factor is less than 0.5
  2. The connections are always wrong
  3. The load is purely resistive
  4. The power factor is unity
Show answer & solution

Answer: (A) The power factor is less than 0.5

The reversed meter must be read with a negative sign.

Question 15

How is the power factor angle φ of a balanced load found from the two-wattmeter readings W1 and W2?

  1. sin φ = W1 − W2
  2. tan φ = √3(W1 − W2)/(W1 + W2)
  3. cos φ = W1/W2
  4. tan φ = (W1 + W2)/(W1 − W2)
Show answer & solution

Answer: (B) tan φ = √3(W1 − W2)/(W1 + W2)

This allows power factor to be measured without a power factor meter.

Question 16

What does the positive-sequence component represent in symmetrical components?

  1. Three equal phasors in phase
  2. A balanced set with reversed phase sequence
  3. An unbalanced set
  4. A balanced set of three phasors with the normal phase sequence
Show answer & solution

Answer: (D) A balanced set of three phasors with the normal phase sequence

Normal balanced operation contains only positive sequence.

Question 17

What does the negative-sequence component represent in symmetrical components?

  1. A DC component
  2. The normal phase sequence
  3. A balanced set of three phasors with reversed phase sequence
  4. Three equal phasors in phase
Show answer & solution

Answer: (C) A balanced set of three phasors with reversed phase sequence

Negative sequence currents overheat generator rotors.

Question 18

What does the zero-sequence component represent in symmetrical components?

  1. A balanced normal sequence
  2. A DC offset
  3. A balanced reversed sequence
  4. Three equal phasors in phase with each other
Show answer & solution

Answer: (D) Three equal phasors in phase with each other

Zero-sequence currents need a neutral or earth return path.

Question 19

What is the value of 1 + a + a², where a is the operator 1∠120°?

  1. Three
  2. √3
  3. Zero
  4. One
Show answer & solution

Answer: (C) Zero

The three unit phasors 120° apart sum to zero.

Question 20

When can zero-sequence current flow in a three-phase system?

  1. Only when there is a path through the neutral or earth
  2. Only in balanced systems
  3. In any isolated system
  4. In a delta system with no earth
Show answer & solution

Answer: (A) Only when there is a path through the neutral or earth

Ungrounded star and delta connections block zero-sequence current from the lines.

Question 21

Why do delta-connected transformer windings help with third harmonic currents?

  1. They create third harmonics
  2. Third harmonics circulate within the delta and do not appear in the lines
  3. They amplify third harmonics
  4. They have no effect
Show answer & solution

Answer: (B) Third harmonics circulate within the delta and do not appear in the lines

Third harmonics behave like zero-sequence quantities.

Question 22

What is the algebraic sum of the three line voltages of a three-phase system at any instant?

  1. Equal to the line voltage
  2. √3 times the phase voltage
  3. Zero
  4. Three times the phase voltage
Show answer & solution

Answer: (C) Zero

The line voltages form a closed triangle of phasors.

Question 23

How many wattmeters are needed to measure power in an unbalanced three-phase four-wire system?

  1. Three
  2. One
  3. Two
  4. Four
Show answer & solution

Answer: (A) Three

Blondel's theorem: n − 1 wattmeters for n wires.

Question 24

What is the equivalent star impedance of a balanced delta load with impedance Z per phase?

  1. Z
  2. Z/3
  3. Z/√3
  4. 3Z
Show answer & solution

Answer: (B) Z/3

Star–delta conversion simplifies three-phase calculations.

Question 25

What is the phase current of a delta-connected load drawing a line current of 17.32 A?

  1. 5.77 A
  2. 10 A
  3. 17.32 A
  4. 30 A
Show answer & solution

Answer: (B) 10 A

Iph = IL/√3 = 17.32/1.732 = 10 A.

Question 26

How is the reactive power of a balanced three-phase load calculated?

  1. VL IL tan φ
  2. √3 VL IL cos φ
  3. 3 VL IL
  4. √3 VL IL sin φ
Show answer & solution

Answer: (D) √3 VL IL sin φ

Q is measured in VAR.

Question 27

Why is per-phase analysis used for balanced three-phase systems?

  1. It removes the need for transformers
  2. Each phase is different
  3. A balanced system can be analysed as one phase and the results applied to all three
  4. It applies only to unbalanced systems
Show answer & solution

Answer: (C) A balanced system can be analysed as one phase and the results applied to all three

The single-phase equivalent uses phase voltage and per-phase impedance.

Question 28

What capacity can an open-delta (V–V) transformer bank supply compared with the original delta–delta bank?

  1. 33.3%
  2. About 57.7%
  3. 66.7%
  4. 100%
Show answer & solution

Answer: (B) About 57.7%

The V–V capacity is 1/√3 of the delta–delta capacity.

Question 29

By how much does the line voltage lead the corresponding phase voltage in a star system with positive phase sequence?

  1. 30°
  2. 60°
  3. 90°
  4. 120°
Show answer & solution

Answer: (A) 30°

VAB leads VAN by 30°.

Question 30

What is the most common phase sequence designation in power systems?

  1. YRB only
  2. BRY only
  3. RBY only
  4. RYB (or ABC)
Show answer & solution

Answer: (D) RYB (or ABC)

Phase sequence is checked with a phase sequence indicator.

Question 31

What happens to the voltage across the phases of an unbalanced star load if the neutral is broken?

  1. Phase voltages become unequal and some loads may get overvoltage
  2. All phase voltages stay equal
  3. Only frequency changes
  4. All voltages become zero
Show answer & solution

Answer: (A) Phase voltages become unequal and some loads may get overvoltage

A sound neutral keeps phase voltages balanced.

Question 32

What causes current in the neutral of a star-connected four-wire distribution system?

  1. Delta-connected loads
  2. Balanced loads only
  3. Unbalanced loading of the phases and triplen harmonics
  4. DC supply
Show answer & solution

Answer: (C) Unbalanced loading of the phases and triplen harmonics

Neutral conductors are sized for unbalance and harmonics.

Question 33

What is the line voltage of a three-phase star system with a phase voltage of 230 V?

  1. 133 V
  2. 230 V
  3. About 400 V
  4. 690 V
Show answer & solution

Answer: (C) About 400 V

VL = √3 × 230 ≈ 398 V.

Question 34

Which instrument checks the phase sequence of a three-phase supply?

  1. Frequency meter
  2. Wattmeter
  3. Megger
  4. Phase sequence indicator
Show answer & solution

Answer: (D) Phase sequence indicator

The direction of rotation of its disc or its lamps shows the sequence.

Question 35

How is power calculated for a three-phase load from per-phase values?

  1. 3 Vph Iph cos φ
  2. √3 Vph Iph cos φ
  3. 3 Vph Iph sin φ
  4. Vph Iph cos φ
Show answer & solution

Answer: (A) 3 Vph Iph cos φ

This equals √3 VL IL cos φ for both star and delta.

Practice these 35 questions interactively →