Question 1

What is the overall heat transfer coefficient U?

  1. The thermal conductivity of the wall
  2. The film coefficient on one side only
  3. The radiation coefficient
  4. A coefficient combining all resistances between hot and cold fluids
Show answer & solution

Answer: (D) A coefficient combining all resistances between hot and cold fluids

1/U = 1/hi + Rwall + 1/ho + fouling, on a consistent area basis.

Question 2

How is the overall coefficient of a clean thin flat wall found from two film coefficients h₁ and h₂ when wall resistance is negligible?

  1. U = h₁ + h₂
  2. 1/U = 1/h₁ + 1/h₂
  3. U = h₁ − h₂
  4. U = h₁ × h₂
Show answer & solution

Answer: (B) 1/U = 1/h₁ + 1/h₂

U is always less than the smaller film coefficient.

Question 3

What is the overall coefficient when h₁ = 100 and h₂ = 100 W/(m²·K) with negligible wall resistance?

  1. 50 W/(m²·K)
  2. 100 W/(m²·K)
  3. 200 W/(m²·K)
  4. 10,000 W/(m²·K)
Show answer & solution

Answer: (A) 50 W/(m²·K)

1/U = 0.01 + 0.01.

Question 4

Which film coefficient controls the overall coefficient?

  1. The fouling factor always
  2. The wall conductivity always
  3. The smaller film coefficient (largest resistance)
  4. The larger film coefficient
Show answer & solution

Answer: (C) The smaller film coefficient (largest resistance)

Improving the controlling side gives the most benefit.

Question 5

What is the log mean temperature difference (LMTD)?

  1. ΔT₁ − ΔT₂
  2. (ΔT₁ + ΔT₂)/2
  3. ΔT₁ × ΔT₂
  4. (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂)
Show answer & solution

Answer: (D) (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂)

It is used in Q = UA·LMTD.

Question 6

What is the LMTD for terminal temperature differences of 60 K and 20 K?

  1. 30 K
  2. About 36.4 K
  3. 40 K
  4. 80 K
Show answer & solution

Answer: (B) About 36.4 K

(60 − 20)/ln 3 = 40/1.0986.

Question 7

What is the LMTD when the two terminal temperature differences are equal?

  1. Infinite
  2. Zero
  3. Equal to that temperature difference
  4. Half that difference
Show answer & solution

Answer: (C) Equal to that temperature difference

The formula becomes 0/0 and the limit is ΔT.

Question 8

Why is counter-current flow preferred to co-current flow in heat exchangers?

  1. It always reduces pressure drop
  2. It gives a larger mean temperature difference and allows closer temperature approach
  3. It removes the need for baffles
  4. It mixes the fluids
Show answer & solution

Answer: (B) It gives a larger mean temperature difference and allows closer temperature approach

The cold outlet can exceed the hot outlet temperature in counter-current flow.

Question 9

In which flow arrangement can the outlet temperature of the cold fluid exceed the outlet temperature of the hot fluid?

  1. Co-current (parallel) flow
  2. Neither arrangement
  3. Only in condensers with parallel flow
  4. Counter-current flow
Show answer & solution

Answer: (D) Counter-current flow

In parallel flow the cold outlet always stays below the hot outlet.

Question 10

What is the LMTD correction factor F used for?

  1. Adjusting the counter-current LMTD for multipass and cross-flow exchangers
  2. Correcting for radiation
  3. Correcting for fouling
  4. Correcting fluid viscosity
Show answer & solution

Answer: (A) Adjusting the counter-current LMTD for multipass and cross-flow exchangers

F values below about 0.75 indicate a poor design.

Question 11

What is a fouling factor?

  1. The flow velocity
  2. The cleaning frequency
  3. An allowance for the extra resistance due to deposits on heat transfer surfaces
  4. The tube thickness
Show answer & solution

Answer: (C) An allowance for the extra resistance due to deposits on heat transfer surfaces

TEMA lists typical fouling resistances.

Question 12

Which standard is widely used for the mechanical design of shell and tube heat exchangers?

  1. ISO 5167
  2. API 650
  3. TEMA standards
  4. IEC 60076
Show answer & solution

Answer: (C) TEMA standards

TEMA classes R, C and B cover severity of service.

Question 13

What is the purpose of baffles on the shell side of a shell and tube exchanger?

  1. To direct shell-side fluid across the tubes, increasing velocity and heat transfer, and to support the tubes
  2. To hold the tube sheet
  3. To separate the tubes from the shell completely
  4. To reduce heat transfer
Show answer & solution

Answer: (A) To direct shell-side fluid across the tubes, increasing velocity and heat transfer, and to support the tubes

Segmental baffles with about 25% cut are common.

Question 14

Which fluid is usually placed on the tube side of a shell and tube exchanger?

  1. Steam always
  2. The more corrosive, fouling or high-pressure fluid
  3. The cleaner low-pressure fluid always
  4. The fluid with the highest viscosity always
Show answer & solution

Answer: (B) The more corrosive, fouling or high-pressure fluid

Tubes are easier to clean and cheaper to make in alloy.

Question 15

What is the purpose of a floating head in a shell and tube exchanger?

  1. To mix fluids
  2. To reduce flow
  3. To increase pressure
  4. To allow differential thermal expansion between tubes and shell and permit bundle removal
Show answer & solution

Answer: (D) To allow differential thermal expansion between tubes and shell and permit bundle removal

Fixed tube-sheet designs may need expansion joints.

Question 16

What is a U-tube heat exchanger's main advantage?

  1. Tubes can expand freely and the bundle can be removed
  2. It has the lowest cost always
  3. It has no tube sheet
  4. Tubes are easy to clean mechanically inside
Show answer & solution

Answer: (A) Tubes can expand freely and the bundle can be removed

Inside cleaning of the U-bends is difficult.

Question 17

What is the effectiveness of a heat exchanger?

  1. The ratio of area to volume
  2. The LMTD
  3. The ratio of actual heat transfer to the maximum possible heat transfer
  4. The ratio of U to h
Show answer & solution

Answer: (C) The ratio of actual heat transfer to the maximum possible heat transfer

ε = Q/Qmax, with Qmax = Cmin(Th,in − Tc,in).

Question 18

What is NTU in heat exchanger analysis?

  1. Cmax/Cmin
  2. Cmin/UA
  3. Q/LMTD
  4. UA/Cmin, the number of transfer units
Show answer & solution

Answer: (D) UA/Cmin, the number of transfer units

The ε–NTU method is useful when outlet temperatures are unknown.

Question 19

What is the heat capacity rate ratio C* in the ε–NTU method?

  1. Cmax/Cmin
  2. Cmin/Cmax
  3. UA/Cmin
  4. Q/Qmax
Show answer & solution

Answer: (B) Cmin/Cmax

For a condenser or evaporator C* = 0.

Question 20

What is the heat duty needed to heat 2 kg/s of water from 30 °C to 70 °C (Cp = 4.18 kJ/(kg·K))?

  1. About 33.4 kW
  2. About 167 kW
  3. About 334 kW
  4. About 3,344 kW
Show answer & solution

Answer: (C) About 334 kW

Q = 2 × 4.18 × 40.

Question 21

What area is needed for a duty of 400 kW with U = 500 W/(m²·K) and LMTD = 40 K?

  1. 10 m²
  2. 20 m²
  3. 40 m²
  4. 200 m²
Show answer & solution

Answer: (B) 20 m²

A = Q/(U·LMTD) = 400,000/20,000.

Question 22

What is a double pipe heat exchanger?

  1. One pipe inside another, with one fluid in the inner pipe and the other in the annulus
  2. A plate exchanger
  3. A cooling tower
  4. Two pipes in parallel
Show answer & solution

Answer: (A) One pipe inside another, with one fluid in the inner pipe and the other in the annulus

It suits small duties and high pressures.

Question 23

What is the main advantage of a plate heat exchanger?

  1. Very high pressure capability
  2. No gaskets
  3. Unlimited temperature range
  4. High heat transfer coefficients and compact size, with easy cleaning
Show answer & solution

Answer: (D) High heat transfer coefficients and compact size, with easy cleaning

Gaskets limit temperature and pressure; they are common in dairies.

Question 24

Which heat exchanger is widely used in dairy pasteurisation?

  1. Plate heat exchanger
  2. Fired heater
  3. Double pipe exchanger only
  4. Air-cooled exchanger
Show answer & solution

Answer: (A) Plate heat exchanger

HTST pasteurisation uses plate exchangers with regeneration sections.

Question 25

What is an air-cooled heat exchanger (fin-fan cooler)?

  1. A refrigerator
  2. An exchanger in which process fluid in finned tubes is cooled by air blown by fans
  3. An exchanger cooled by sea water
  4. A cooling tower
Show answer & solution

Answer: (B) An exchanger in which process fluid in finned tubes is cooled by air blown by fans

It saves cooling water in dry areas.

Question 26

What is a reboiler in a distillation system?

  1. A condenser at the top
  2. A pump
  3. A feed preheater only
  4. A heat exchanger that vaporises liquid at the bottom of the column
Show answer & solution

Answer: (D) A heat exchanger that vaporises liquid at the bottom of the column

Kettle and thermosiphon reboilers are common.

Question 27

What does a thermosiphon reboiler rely on for circulation?

  1. A pump
  2. A fan
  3. Density difference between liquid and the vapour–liquid mixture
  4. Gravity flow of vapour only
Show answer & solution

Answer: (C) Density difference between liquid and the vapour–liquid mixture

Vertical thermosiphon reboilers are common in refineries.

Question 28

What is a regenerator?

  1. An evaporator
  2. A boiler
  3. A heat exchanger where hot and cold fluids flow alternately through the same matrix that stores heat
  4. A double pipe exchanger
Show answer & solution

Answer: (C) A heat exchanger where hot and cold fluids flow alternately through the same matrix that stores heat

Glass furnaces and blast-furnace stoves use regenerators.

Question 29

What is an economiser in a boiler?

  1. A steam superheater
  2. A fuel pump
  3. A chimney damper
  4. A heat exchanger that preheats boiler feedwater using flue gas
Show answer & solution

Answer: (D) A heat exchanger that preheats boiler feedwater using flue gas

It raises boiler efficiency.

Question 30

What is the purpose of an air preheater in a furnace?

  1. To heat combustion air with flue gas, saving fuel
  2. To compress air
  3. To remove dust
  4. To cool the furnace
Show answer & solution

Answer: (A) To heat combustion air with flue gas, saving fuel

Flue gas exit temperature must stay above the acid dew point.

Question 31

Why are cooling-water outlet temperatures kept below about 45–50 °C?

  1. To increase corrosion
  2. To limit scaling and fouling on heat exchanger surfaces
  3. To avoid freezing
  4. To raise heat transfer
Show answer & solution

Answer: (B) To limit scaling and fouling on heat exchanger surfaces

Hardness salts deposit faster at higher temperatures.

Question 32

What is the jacket of a reactor vessel used for?

  1. Mixing the contents
  2. Measuring level
  3. Heating or cooling the vessel contents by fluid circulating in an outer shell
  4. Supporting the vessel
Show answer & solution

Answer: (C) Heating or cooling the vessel contents by fluid circulating in an outer shell

Internal coils give more area when needed.

Question 33

What is the approach temperature in a heat exchanger?

  1. The largest temperature difference
  2. The hot inlet temperature
  3. The ambient temperature
  4. The smallest temperature difference between hot and cold streams
Show answer & solution

Answer: (D) The smallest temperature difference between hot and cold streams

Small approaches need large areas.

Question 34

How does fouling affect heat exchanger performance over time?

  1. It has no effect
  2. It lowers U, reducing duty and often increasing pressure drop
  3. It increases U
  4. It raises the LMTD
Show answer & solution

Answer: (B) It lowers U, reducing duty and often increasing pressure drop

Periodic cleaning restores performance.

Question 35

What is a scraped-surface heat exchanger used for?

  1. Heating or cooling very viscous or crystallising products
  2. Gas cooling
  3. Steam generation
  4. Air conditioning
Show answer & solution

Answer: (A) Heating or cooling very viscous or crystallising products

Rotating blades keep the surface clean.

Question 36

What is the typical overall coefficient for a steam-to-water shell and tube heat exchanger?

  1. About 5 to 20 W/(m²·K)
  2. About 50 W/(m²·K)
  3. About 1,000 to 3,500 W/(m²·K)
  4. About 100,000 W/(m²·K)
Show answer & solution

Answer: (C) About 1,000 to 3,500 W/(m²·K)

Gas-to-gas exchangers have much lower values.

Question 37

What is the hot-fluid outlet temperature if 1 kg/s of oil (Cp = 2 kJ/(kg·K)) at 150 °C gives 100 kW to water?

  1. 50 °C
  2. 75 °C
  3. 100 °C
  4. 125 °C
Show answer & solution

Answer: (C) 100 °C

ΔT = 100/(1 × 2) = 50 K.

Question 38

What is the maximum possible heat transfer in an exchanger with Cmin = 4 kW/K and inlet temperatures 120 °C (hot) and 20 °C (cold)?

  1. 4 kW
  2. 80 kW
  3. 400 kW
  4. 480 kW
Show answer & solution

Answer: (C) 400 kW

Qmax = Cmin × (Th,in − Tc,in).

Question 39

What is the heat exchanger effectiveness if actual duty is 300 kW and maximum possible duty is 400 kW?

  1. 0.25
  2. 0.4
  3. 0.75
  4. 1.33
Show answer & solution

Answer: (C) 0.75

ε = 300/400.

Question 40

What is a 1-2 shell and tube heat exchanger?

  1. A plate exchanger with two plates
  2. An exchanger with one shell pass and two tube passes
  3. One shell and one tube pass
  4. Two shells and one tube pass
Show answer & solution

Answer: (B) An exchanger with one shell pass and two tube passes

Multi-pass designs need the LMTD correction factor.

Question 41

Why is the tube pitch arranged in a triangular pattern in many exchangers?

  1. It makes mechanical cleaning outside the tubes easiest
  2. It removes the need for baffles
  3. It reduces heat transfer
  4. It fits more tubes in a given shell and gives higher shell-side coefficients
Show answer & solution

Answer: (D) It fits more tubes in a given shell and gives higher shell-side coefficients

Square pitch is preferred where the shell side must be cleaned mechanically.

Question 42

What is pinch analysis used for?

  1. Designing heat exchanger networks to minimise external heating and cooling utilities
  2. Sizing pipes
  3. Designing pumps
  4. Measuring fouling
Show answer & solution

Answer: (A) Designing heat exchanger networks to minimise external heating and cooling utilities

It identifies the minimum temperature approach point between composite curves.

Question 43

What is a waste heat boiler?

  1. A boiler that raises steam from hot process or flue gas
  2. A boiler fired with waste oil only
  3. A water heater
  4. A condenser
Show answer & solution

Answer: (A) A boiler that raises steam from hot process or flue gas

It is used after sulphur furnaces and reformers.

Practice these 43 questions interactively →