Engineering, Management, Agriculture and Veterinary MCQs are now live. FPSC, PPSC, EPE, IELTS & GRE coming soon.

Process Control & Instrumentation: Control Valves and Systems

Chemical Engineering · Process Control & Instrumentation

34 questions, each with the answer and a worked solution.

Practice interactively and track your score →
Question 1

What is the function of a control valve?

  1. To measure flow
  2. To measure pressure
  3. To store fluid
  4. To adjust flow of a fluid in response to a controller signal
Show answer & solution

Answer: (D) To adjust flow of a fluid in response to a controller signal

It is the most common final control element.

Question 2

What is a fail-closed (air-to-open) valve?

  1. A valve that closes on loss of air signal
  2. A valve that stays in place
  3. A valve that opens on loss of air
  4. A manual valve
Show answer & solution

Answer: (A) A valve that closes on loss of air signal

Fuel valves to furnaces are fail-closed.

Question 3

What is a fail-open (air-to-close) valve used for?

  1. Fuel supply to furnaces
  2. Services where loss of signal should open the valve, such as cooling water to an exothermic reactor
  3. Feed to reactors always
  4. Steam to heaters
Show answer & solution

Answer: (B) Services where loss of signal should open the valve, such as cooling water to an exothermic reactor

Fail-safe action is chosen for process safety.

Question 4

What is the inherent characteristic of a valve?

  1. The installed flow under varying pressure drop
  2. The valve material
  3. The valve size
  4. The relation between flow and valve stem travel at constant pressure drop
Show answer & solution

Answer: (D) The relation between flow and valve stem travel at constant pressure drop

Linear, equal percentage and quick opening are common.

Question 5

What is an equal-percentage valve characteristic?

  1. Flow independent of travel
  2. Flow proportional to stem travel
  3. Equal increments of stem travel give equal percentage changes in existing flow
  4. Most flow change in the first part of travel
Show answer & solution

Answer: (C) Equal increments of stem travel give equal percentage changes in existing flow

It is the most common choice in process control.

Question 6

Which valve characteristic is suited to on–off service?

  1. Quick opening
  2. Linear
  3. Parabolic modified
  4. Equal percentage
Show answer & solution

Answer: (A) Quick opening

Large flow change occurs at small opening.

Question 7

Why is an equal-percentage valve often preferred when pressure drop across the valve falls with increasing flow?

  1. Its installed characteristic becomes more nearly linear
  2. It removes pump curves
  3. It becomes quick opening
  4. It has no characteristic
Show answer & solution

Answer: (A) Its installed characteristic becomes more nearly linear

System pressure losses distort the inherent characteristic.

Question 8

What is the valve flow coefficient Cv?

  1. The valve diameter
  2. The pressure rating
  3. The stem travel
  4. The flow of water in US gallons per minute at 1 psi pressure drop across the fully open valve
Show answer & solution

Answer: (D) The flow of water in US gallons per minute at 1 psi pressure drop across the fully open valve

Kv is the metric equivalent in m³/h at 1 bar.

Question 9

How does liquid flow through a valve depend on pressure drop?

  1. Independently of ΔP
  2. In proportion to ΔP²
  3. In proportion to Cv √(ΔP/SG)
  4. In proportion to ΔP
Show answer & solution

Answer: (C) In proportion to Cv √(ΔP/SG)

SG is specific gravity relative to water.

Question 10

What is valve rangeability?

  1. The leakage class
  2. The ratio of maximum to minimum controllable flow
  3. The valve size
  4. The pressure rating
Show answer & solution

Answer: (B) The ratio of maximum to minimum controllable flow

Typical values are 30:1 to 100:1.

Question 11

What is flashing in a control valve?

  1. Bubbles forming and then collapsing
  2. Air entry
  3. Leakage at the stem
  4. Liquid partly vaporising when pressure falls below vapour pressure and does not recover
Show answer & solution

Answer: (D) Liquid partly vaporising when pressure falls below vapour pressure and does not recover

Cavitation occurs if pressure recovers above vapour pressure, collapsing bubbles.

Question 12

What is a valve positioner?

  1. A pressure switch
  2. A device that ensures the valve stem reaches the position demanded by the controller signal
  3. A flow meter
  4. A manual handwheel
Show answer & solution

Answer: (B) A device that ensures the valve stem reaches the position demanded by the controller signal

It overcomes friction and improves response.

Question 13

Which valve type is commonly used for throttling control in process plants?

  1. Globe valve
  2. Plug cock
  3. Butterfly in tight shut-off only
  4. Gate valve
Show answer & solution

Answer: (A) Globe valve

Gate valves are for isolation, not throttling.

Question 14

Which valve type gives low pressure drop and is used for large-diameter flows such as cooling water?

  1. Needle valve
  2. Diaphragm valve
  3. Butterfly valve
  4. Globe valve
Show answer & solution

Answer: (C) Butterfly valve

It is compact and cheap.

Question 15

What is a valve actuator?

  1. The controller
  2. The device that moves the valve stem, usually pneumatic diaphragm, piston or electric motor
  3. The valve seat
  4. The valve body
Show answer & solution

Answer: (B) The device that moves the valve stem, usually pneumatic diaphragm, piston or electric motor

Spring-diaphragm actuators provide fail-safe action.

Question 16

What is stiction in control valves?

  1. Leakage
  2. Noise
  3. Static friction that prevents smooth movement, causing stick–slip and oscillations
  4. Fast response
Show answer & solution

Answer: (C) Static friction that prevents smooth movement, causing stick–slip and oscillations

It is a common cause of loop oscillation.

Question 17

What is a P&ID?

  1. Piping and instrumentation diagram showing equipment, piping, instruments and control loops
  2. A process flow diagram with only mass balances
  3. A plot plan
  4. A wiring diagram only
Show answer & solution

Answer: (A) Piping and instrumentation diagram showing equipment, piping, instruments and control loops

Symbols follow ISA-5.1.

Question 18

What does the instrument tag TIC stand for?

  1. Transmitter input card
  2. Total instrument control
  3. Temperature integrating converter
  4. Temperature indicating controller
Show answer & solution

Answer: (D) Temperature indicating controller

The first letter is the measured variable.

Question 19

What does the tag FT represent on a P&ID?

  1. Feed temperature
  2. Flow transmitter
  3. Filter tank
  4. Fail-safe trip
Show answer & solution

Answer: (B) Flow transmitter

ISA-5.1 symbols are used worldwide.

Question 20

What does LAH stand for in instrumentation?

  1. Low air heater
  2. Level actuator handle
  3. Line air header
  4. Level alarm high
Show answer & solution

Answer: (D) Level alarm high

LALL denotes a low-low alarm.

Question 21

What is a distributed control system (DCS)?

  1. A wireless sensor
  2. A manual control panel
  3. A computer-based control system with controllers distributed across the plant and central operator stations
  4. A single analogue controller
Show answer & solution

Answer: (C) A computer-based control system with controllers distributed across the plant and central operator stations

Most Pakistani refineries and fertiliser plants use DCS.

Question 22

What is a PLC?

  1. A programmable logic controller used mainly for sequential, interlock and discrete control
  2. A pressure level controller
  3. A pump lubrication circuit
  4. A piping layout chart
Show answer & solution

Answer: (A) A programmable logic controller used mainly for sequential, interlock and discrete control

PLCs are common in packaging and batch plants.

Question 23

What is SCADA?

  1. A type of pump
  2. A distillation method
  3. Supervisory control and data acquisition for monitoring and controlling geographically spread facilities
  4. A single control valve
Show answer & solution

Answer: (C) Supervisory control and data acquisition for monitoring and controlling geographically spread facilities

It is used for gas pipelines and water distribution.

Question 24

What is an interlock?

  1. An automatic action that prevents unsafe operation or shuts down equipment when conditions are unsafe
  2. A flow meter
  3. A controller tuning method
  4. A manual valve
Show answer & solution

Answer: (A) An automatic action that prevents unsafe operation or shuts down equipment when conditions are unsafe

For example, burner trip on flame failure.

Question 25

What is a pressure safety valve (PSV) used for?

  1. Measuring pressure
  2. Automatically relieving excess pressure to protect equipment
  3. Controlling flow continuously
  4. Isolating pipelines
Show answer & solution

Answer: (B) Automatically relieving excess pressure to protect equipment

PSV sizing follows API 520 and API 521 guidance.

Question 26

What is the purpose of a rupture disc?

  1. To regulate pressure continuously
  2. To measure flow
  3. To control temperature
  4. To burst at a set pressure, providing fast pressure relief
Show answer & solution

Answer: (D) To burst at a set pressure, providing fast pressure relief

It is not reclosing.

Question 27

What is the purpose of a check (non-return) valve?

  1. To throttle flow
  2. To relieve pressure
  3. To allow flow in one direction only
  4. To measure flow
Show answer & solution

Answer: (C) To allow flow in one direction only

It prevents backflow, for example at pump discharge.

Question 28

What is the turndown of a control loop limited by?

  1. Controller brand
  2. Valve rangeability and measurement range
  3. Operator experience only
  4. Pipe colour
Show answer & solution

Answer: (B) Valve rangeability and measurement range

Oversized valves give poor control at low flows.

Question 29

Why should control valves not be oversized?

  1. They operate nearly closed, giving poor resolution and unstable control
  2. They reduce pressure drop
  3. They give better control
  4. They save cost always
Show answer & solution

Answer: (A) They operate nearly closed, giving poor resolution and unstable control

Typical design opening is 60–80% at normal flow.

Question 30

What is the meaning of the letter C as a succeeding letter in an ISA tag such as LC?

  1. Current
  2. Conductivity
  3. Controller
  4. Cooler
Show answer & solution

Answer: (C) Controller

The first letter gives the measured variable.

Question 31

What does the tag PSV mean on a P&ID?

  1. Pressure sample valve
  2. Process steam vent
  3. Pump suction valve
  4. Pressure safety valve
Show answer & solution

Answer: (D) Pressure safety valve

It protects equipment from overpressure.

Question 32

What is the purpose of a hand switch (HS) on a P&ID?

  1. To allow manual start, stop or selection of equipment
  2. To relieve pressure
  3. To measure flow
  4. To control temperature automatically
Show answer & solution

Answer: (A) To allow manual start, stop or selection of equipment

H denotes hand (manual).

Question 33

What is a solenoid valve?

  1. A throttling globe valve
  2. An electrically operated on–off valve
  3. A manual valve
  4. A safety valve
Show answer & solution

Answer: (B) An electrically operated on–off valve

It is used in interlocks and pneumatic actuator control.

Question 34

What is the function of an I/P converter?

  1. To power a transmitter
  2. To convert a 4–20 mA electrical signal into a 3–15 psi pneumatic signal for a valve actuator
  3. To measure current
  4. To convert pressure into level
Show answer & solution

Answer: (B) To convert a 4–20 mA electrical signal into a 3–15 psi pneumatic signal for a valve actuator

Positioners often include it.

Practice these 34 questions interactively →