What is the working principle of a thermocouple?
Show answer & solution
Answer: (B) The Seebeck effect, a voltage produced at the junction of two dissimilar metals at different temperatures
The cold junction must be compensated.
Chemical Engineering · Process Control & Instrumentation
37 questions, each with the answer and a worked solution.
Practice interactively and track your score →What is the working principle of a thermocouple?
Answer: (B) The Seebeck effect, a voltage produced at the junction of two dissimilar metals at different temperatures
The cold junction must be compensated.
Which thermocouple type is most widely used for general industrial temperatures up to about 1,200 °C?
Answer: (A) Type K (chromel–alumel)
Type S and B are used at higher temperatures.
Which thermocouple types are used for very high temperatures such as in furnaces and glass melting?
Answer: (D) Types R, S and B based on platinum–rhodium
They are expensive but stable.
What is a resistance temperature detector (RTD)?
Answer: (C) A sensor whose electrical resistance changes with temperature, usually platinum
Pt100 has 100 Ω at 0 °C.
What is the resistance of a Pt100 RTD at 0 °C?
Answer: (C) 100 Ω
Pt1000 has 1,000 Ω at 0 °C.
What is a thermistor?
Answer: (A) A semiconductor resistor with a large, often negative, temperature coefficient
It is very sensitive over a narrow range.
What is the purpose of a thermowell?
Answer: (B) To protect a temperature sensor from the process fluid while allowing heat transfer
It adds a lag to the measurement.
Which instrument measures temperature by the bending of two bonded metals with different expansion coefficients?
Answer: (A) Bimetallic thermometer
It is used in local gauges and thermostats.
What is a differential pressure (DP) transmitter used for in level measurement?
Answer: (D) Measuring hydrostatic head of liquid to infer level
Level = ΔP/(ρg); density changes cause error.
Which level measurement uses a buoyant element whose apparent weight changes with level?
Answer: (B) Displacer level transmitter
Floats follow the surface instead.
Which non-contact level measurement uses microwaves reflected from the liquid surface?
Answer: (C) Radar level transmitter
It is unaffected by vapour and temperature changes.
What is a bubbler (purge) level system?
Answer: (D) A system that measures the back-pressure of air bubbled through a dip tube to find level
It suits corrosive or slurry liquids.
What is a sight glass?
Answer: (A) A transparent tube or window showing liquid level directly
It is used for local indication.
What is a nuclear (radiation) level gauge suited for?
Answer: (B) Level measurement in highly corrosive, hot or high-pressure vessels without contact
A source and detector are placed outside the vessel.
Which device converts pressure into electrical signal using a deforming diaphragm?
Answer: (B) Pressure transmitter with strain gauge or capacitive sensor
Smart transmitters also send digital diagnostics.
What is the standard analogue signal range for electronic process transmitters?
Answer: (D) 4 to 20 mA
A 4 mA live zero helps detect broken wires.
What is the standard pneumatic signal range for process instruments?
Answer: (C) 3 to 15 psi (about 0.2 to 1.0 bar)
Pneumatic valves are still widely used.
What does a 12 mA signal represent on a 4–20 mA transmitter with range 0–200 °C?
Answer: (C) 100 °C
12 mA is 50% of the 16 mA span.
Which instrument measures pH?
Answer: (A) A glass electrode with a reference electrode
The electrode produces about 59 mV per pH unit at 25 °C.
What principle does a gas chromatograph use for composition analysis?
Answer: (A) Separation of components in a column by different retention times, followed by detection
Online GCs are used in refineries and gas plants.
What does a conductivity analyser measure in water treatment?
Answer: (D) Total dissolved ionic content of water
It monitors boiler water and RO permeate quality.
What is the accuracy of an instrument?
Answer: (B) The closeness of a measurement to the true value
Precision describes repeatability.
What is the span of an instrument with a range of 50 to 250 °C?
Answer: (B) 200 °C
Span = upper range − lower range.
What is hysteresis in an instrument?
Answer: (C) A difference in output for the same input approached from increasing and decreasing directions
Friction and magnetic effects cause hysteresis.
What is the dead band of an instrument?
Answer: (D) The range of input change that produces no detectable output change
Valve stiction creates dead band.
What does HART protocol allow?
Answer: (A) Digital communication superimposed on a 4–20 mA analogue signal
It is used for configuration and diagnostics.
Which fieldbus standards are used for digital communication among field devices?
Answer: (B) Foundation Fieldbus and PROFIBUS PA
They carry multiple variables on one cable.
What is calibration of an instrument?
Answer: (C) Comparing its readings against a known standard and adjusting it
Zero and span are adjusted.
What is cold junction compensation in thermocouple circuits?
Answer: (B) Correcting for the temperature of the reference junction where thermocouple wires connect to the instrument
Extension wires of matching alloy are used.
Why are RTDs often preferred over thermocouples for moderate temperatures?
Answer: (A) They are more accurate and stable
Thermocouples suit higher temperatures and fast response.
What is an infrared pyrometer used for?
Answer: (C) Non-contact temperature measurement of hot or moving surfaces
Emissivity must be set correctly.
What is a Bourdon tube gauge used for?
Answer: (B) Local pressure indication
It is the most common mechanical pressure gauge.
What is a capacitance level probe based on?
Answer: (C) Change in capacitance as the level of material between electrodes changes
It suits many liquids and powders.
What is the response time of a measuring element?
Answer: (D) The time it takes to respond to a change in the measured variable, often characterised by a time constant
Sensor lags add to loop dynamics.
Which analyser monitors oxygen in flue gas for combustion control?
Answer: (A) Zirconia oxygen analyser
It works at high temperature in situ.
What is a strain gauge?
Answer: (B) A sensor whose resistance changes with mechanical strain, used in load cells and pressure sensors
Wheatstone bridges measure the small changes.
What does a load cell measure?
Answer: (C) Weight or force
Weighing of tanks and hoppers uses load cells.