What is feedback control?
Show answer & solution
Answer: (D) Control in which the controlled variable is measured and compared with the set point to adjust the manipulated variable
It corrects for all disturbances after they affect the process.
Chemical Engineering · Process Control & Instrumentation
34 questions, each with the answer and a worked solution.
Practice interactively and track your score →What is feedback control?
Answer: (D) Control in which the controlled variable is measured and compared with the set point to adjust the manipulated variable
It corrects for all disturbances after they affect the process.
What is the set point?
Answer: (A) The desired value of the controlled variable
Error = set point − measured value.
What is the manipulated variable?
Answer: (A) The variable adjusted by the controller to keep the controlled variable at set point
Usually a flow adjusted by a control valve.
What is a disturbance (load) variable?
Answer: (D) An input that affects the controlled variable but is not adjusted by the controller
Feed composition changes are typical disturbances.
What is offset in proportional control?
Answer: (B) A sustained steady-state error between set point and controlled variable
Proportional-only control usually leaves offset for load changes.
What is the transfer function of an ideal PID controller?
Answer: (C) Kc(1 + 1/(τIs) + τDs)
τI is integral time and τD derivative time.
What is the main advantage of integral action?
Answer: (C) It eliminates offset
It may cause overshoot and reset windup.
What is the main purpose of derivative action?
Answer: (A) It anticipates the error by responding to its rate of change, improving stability
It is avoided on noisy signals such as flow.
Why is derivative action seldom used in flow control loops?
Answer: (B) Flow signals are noisy and the process is fast
PI control is standard for flow.
Which controller mode is most common in liquid flow control?
Answer: (D) PI
Flow loops are fast and noisy.
What is proportional band?
Answer: (C) The percentage change in input needed to drive the controller output through its full range
PB = 100/Kc for dimensionless gain.
What is the proportional band of a controller with gain 2?
Answer: (C) 50%
PB = 100/2.
What is reset windup?
Answer: (A) Integral action accumulating a large output when the final element is saturated, causing overshoot
Anti-windup logic limits the integral term.
What is derivative kick?
Answer: (B) A spike in controller output caused by a sudden set point change acting on derivative action
Derivative on measurement avoids it.
What is on–off control?
Answer: (D) Control in which the final element is either fully open or fully closed
A dead band (differential gap) reduces cycling; home thermostats use it.
What is direct action of a controller?
Answer: (A) Controller output increases as measured value increases
Action must match valve type and process gain to give negative feedback.
What is the Ziegler–Nichols closed-loop (ultimate gain) method?
Answer: (B) Finding the gain at which the loop oscillates continuously and its period, then calculating settings
For a PI controller Kc = 0.45Ku and τI = Pu/1.2.
What proportional gain does Ziegler–Nichols recommend for a P-only controller?
Answer: (D) 0.5 Ku
For PID it is 0.6 Ku.
What is the Cohen–Coon method?
Answer: (B) A tuning method based on first-order-plus-dead-time parameters from an open-loop step test
It suits processes with significant dead time.
Which integral error criterion penalises errors persisting for a long time most heavily?
Answer: (C) ITAE (integral of time-weighted absolute error)
ISE penalises large errors heavily.
What is the effect of increasing proportional gain in a feedback loop?
Answer: (A) Faster response and less offset, but more oscillation and eventual instability
Excessive gain makes the loop unstable.
What is the closed-loop transfer function for set point changes in a simple feedback loop?
Answer: (D) GcGvGp/(1 + GcGvGpGm)
The denominator gives the characteristic equation.
What is the characteristic equation of a feedback loop?
Answer: (D) 1 + open-loop transfer function = 0
Its roots determine stability.
What is a servo problem in control?
Answer: (C) Following changes in set point
A regulator problem deals with disturbances at fixed set point.
What does integral time τI represent?
Answer: (A) The time for integral action to repeat the proportional action for a constant error
Some controllers use reset rate = 1/τI in repeats per minute.
What is a controller's bumpless transfer?
Answer: (B) Switching between manual and automatic without a sudden jump in output
Modern controllers track output in manual mode.
What is the steady-state error of a type-1 loop (with integral action) to a step change in set point?
Answer: (A) Zero
Integral action gives zero steady-state error to steps.
What is a good starting controller type for liquid level in a surge tank where tight control is not needed?
Answer: (D) P or PI with low gain to use the tank capacity (averaging control)
Averaging level control smooths outflow.
Which controller mode is commonly used for slow temperature loops with large lags?
Answer: (C) PID
Derivative action helps with large time constants.
What is the controllability ratio θ/τ used for?
Answer: (D) Judging how difficult a process is to control; larger ratios are harder
Dead-time-dominant processes have high ratios.
What happens if a controller's action is set wrongly (direct instead of reverse)?
Answer: (A) Positive feedback drives the process away from set point
Action must give negative feedback.
What is the reset rate of a controller with integral time 2 min?
Answer: (A) 0.5 repeats per minute
Reset rate = 1/τI.
What is the PID tuning rule for internal model control (IMC) based on?
Answer: (C) A process model and a single closed-loop time constant parameter
It gives robust settings for FOPDT models.
What is the role of the measuring element in a feedback loop?
Answer: (D) To measure the controlled variable and send a signal to the controller
Measurement lags add to loop dynamics.