Question 1
- A controller with feedforward only
- Two controllers in parallel
- On–off control
- A strategy in which a primary controller sets the set point of a secondary controller on a faster inner loop
Show answer & solution
Answer: (D) A strategy in which a primary controller sets the set point of a secondary controller on a faster inner loop
It rejects disturbances in the inner loop before they affect the primary variable.
Question 2
What is a typical example of cascade control?
- A single level controller
- Reactor temperature controller adjusting the set point of a jacket coolant flow controller
- A ratio of two flows
- Manual valve operation
Show answer & solution
Answer: (B) Reactor temperature controller adjusting the set point of a jacket coolant flow controller
The inner flow loop must be faster than the outer loop.
Question 3
What is a requirement for effective cascade control?
- The inner loop must be slower
- Both loops must have the same speed
- No measurement of the secondary variable
- The secondary (inner) loop must respond faster than the primary loop
Show answer & solution
Answer: (D) The secondary (inner) loop must respond faster than the primary loop
Inner loops are often three to five times faster.
Question 4
What is feedforward control?
- Control that measures a disturbance and adjusts the manipulated variable before the controlled variable is affected
- Manual control
- On–off control
- Control based only on error
Show answer & solution
Answer: (A) Control that measures a disturbance and adjusts the manipulated variable before the controlled variable is affected
It needs a good process model.
Question 5
Why is feedforward usually combined with feedback?
- Feedback needs no sensors
- Feedforward is always perfect
- Feedback is slower
- Feedforward cannot correct for unmeasured disturbances and model errors
Show answer & solution
Answer: (D) Feedforward cannot correct for unmeasured disturbances and model errors
The combination gives fast and accurate control.
Question 6
What is the ideal feedforward controller transfer function?
- −Gd/Gp, the negative ratio of disturbance and process transfer functions
- Gp/Gd
- Kc(1 + 1/τIs)
- 1/(τs + 1)
Show answer & solution
Answer: (A) −Gd/Gp, the negative ratio of disturbance and process transfer functions
It may not be physically realisable if Gd is faster than Gp.
Question 7
- Keeping one flow constant
- Keeping the ratio of two flows constant, such as fuel to air in a furnace
- Controlling temperature by on–off
- Controlling pressure only
Show answer & solution
Answer: (B) Keeping the ratio of two flows constant, such as fuel to air in a furnace
The wild flow is measured and the controlled flow is set as a ratio.
Question 8
What is a common example of ratio control in a boiler?
- Maintaining drum level
- Maintaining feedwater temperature
- Maintaining air-to-fuel ratio
- Maintaining steam pressure only
Show answer & solution
Answer: (C) Maintaining air-to-fuel ratio
Cross-limiting logic prevents fuel-rich conditions.
Question 9
What is three-element control of a boiler drum?
- Control of three boilers
- Control with three valves
- Drum level control using level, steam flow and feedwater flow measurements
- Control of pressure, temperature and flow independently
Show answer & solution
Answer: (C) Drum level control using level, steam flow and feedwater flow measurements
Steam flow acts as feedforward to overcome shrink and swell.
Question 10
What is split-range control?
- One controller output operating two or more final elements over different parts of its range
- Ratio control
- Cascade control
- Two controllers on one valve
Show answer & solution
Answer: (A) One controller output operating two or more final elements over different parts of its range
For example heating and cooling valves on a reactor.
Question 11
What is override (selective) control?
- Manual override only
- Control with no limits
- Feedforward control
- Using a selector to choose between controller outputs to protect equipment from limits
Show answer & solution
Answer: (D) Using a selector to choose between controller outputs to protect equipment from limits
High or low selectors are used, for example for compressor protection.
Question 12
What is auctioneering control?
- Averaging all sensors
- Selecting the highest (or lowest) of several measurements as the controlled variable
- Using no sensor
- Selecting a random sensor
Show answer & solution
Answer: (B) Selecting the highest (or lowest) of several measurements as the controlled variable
For example controlling the hottest point in a reactor bed.
Question 13
What is a Smith predictor?
- An on–off controller
- A feedforward controller
- A dead-time compensator that uses a process model to remove the dead time from the feedback path
- A ratio controller
Show answer & solution
Answer: (C) A dead-time compensator that uses a process model to remove the dead time from the feedback path
Its performance depends on model accuracy.
Question 14
What is model predictive control (MPC)?
- Manual control
- An advanced method that uses a dynamic model to predict future outputs and optimise control moves within constraints
- Simple PID control
- On–off control
Show answer & solution
Answer: (B) An advanced method that uses a dynamic model to predict future outputs and optimise control moves within constraints
It is widely used in refineries for multivariable units.
Question 15
What is the relative gain array (RGA) used for?
- Selecting sensors
- Sizing valves
- Tuning a single PID loop
- Selecting the best pairing of controlled and manipulated variables in multivariable systems
Show answer & solution
Answer: (D) Selecting the best pairing of controlled and manipulated variables in multivariable systems
Pairings with relative gains close to 1 are preferred.
Question 16
What does a negative relative gain indicate for a proposed pairing?
- The pairing should be avoided because it can cause instability when other loops are closed
- An ideal pairing
- No interaction
- A fast response
Show answer & solution
Answer: (A) The pairing should be avoided because it can cause instability when other loops are closed
Relative gains near 1 are best.
Question 17
What is loop interaction?
- One control loop affecting the controlled variable of another loop
- A failed transmitter
- A slow valve
- A loop with no disturbances
Show answer & solution
Answer: (A) One control loop affecting the controlled variable of another loop
Decouplers can reduce interaction.
Question 18
What is adaptive control?
- On–off control
- Fixed-gain control
- Feedforward only
- Control in which controller parameters are adjusted automatically as process characteristics change
Show answer & solution
Answer: (D) Control in which controller parameters are adjusted automatically as process characteristics change
Gain scheduling is a simple form.
Question 19
What is inferential control?
- Controlling with direct composition analysers only
- Controlling an unmeasured variable by using related measurable variables to estimate it
- Feedforward only
- Manual control
Show answer & solution
Answer: (B) Controlling an unmeasured variable by using related measurable variables to estimate it
Tray temperature is used to infer composition in distillation.
Question 20
What is the typical controlled variable used instead of composition for distillation column control?
- Cooling water temperature
- Reflux drum pressure only
- A sensitive tray temperature
- Feed flow
Show answer & solution
Answer: (C) A sensitive tray temperature
Online analysers are slower and costlier.
Question 21
What is the purpose of a safety instrumented system (SIS)?
- To measure flow
- To control normal operation
- To tune PID loops
- To bring the process to a safe state independently of the basic control system when limits are exceeded
Show answer & solution
Answer: (D) To bring the process to a safe state independently of the basic control system when limits are exceeded
Its design follows IEC 61511 for the process industry.
Question 22
Which international standard covers functional safety of safety instrumented systems in the process industry?
- API 650
- ISO 9001
- IEC 61511
- ASME B31.3
Show answer & solution
Answer: (C) IEC 61511
Safety integrity levels (SIL 1 to 4) define the required reliability.
Question 23
Why is feedforward control well suited to heat exchangers with variable feed flow?
- Feed flow changes can be measured and corrected before outlet temperature deviates
- Feed flow cannot be measured
- It eliminates the need for steam
- Feedback is not possible
Show answer & solution
Answer: (A) Feed flow changes can be measured and corrected before outlet temperature deviates
Steady-state feedforward uses an energy balance.
Question 24
What is static (steady-state) feedforward?
- Feedback control
- Feedforward based only on steady-state gains without dynamic compensation
- Manual control
- Feedforward with lead–lag terms
Show answer & solution
Answer: (B) Feedforward based only on steady-state gains without dynamic compensation
Lead–lag units add dynamic compensation.
Question 25
What is a lead–lag element used for in feedforward control?
- Matching the dynamics of the disturbance and manipulated variable paths
- Measuring flow
- Tuning PID loops
- Increasing gain
Show answer & solution
Answer: (A) Matching the dynamics of the disturbance and manipulated variable paths
Its transfer function is (τ₁s + 1)/(τ₂s + 1).
Question 26
What is decoupling control?
- Ratio control
- Using on–off control
- Removing all controllers
- Adding compensators so that each manipulated variable affects mainly its own controlled variable
Show answer & solution
Answer: (D) Adding compensators so that each manipulated variable affects mainly its own controlled variable
It reduces interaction in multivariable systems.
Question 27
- Fixing all gains
- Removing integral action
- Changing controller tuning according to an operating variable such as throughput
- Setting gain to zero
Show answer & solution
Answer: (C) Changing controller tuning according to an operating variable such as throughput
It handles non-linear processes.
Question 28
What is valve position control?
- Adjusting a set point slowly to keep a control valve near a desired opening for efficiency
- Controlling stem leakage
- Measuring valve size
- Manual valve setting
Show answer & solution
Answer: (A) Adjusting a set point slowly to keep a control valve near a desired opening for efficiency
It is used to minimise compressor pressure or pumping energy.
Question 29
What is the main benefit of real-time optimisation (RTO) above advanced control layers?
- Tuning valves
- Replacing all sensors
- Calculating optimal set points economically for the controllers
- Measuring temperature
Show answer & solution
Answer: (C) Calculating optimal set points economically for the controllers
It uses steady-state process models.
Question 30
What is the hierarchy of control layers in a modern plant?
- Only manual control
- Basic regulatory control, advanced control (MPC), and optimisation, with safety systems independent
- Optimisation only
- Safety only
Show answer & solution
Answer: (B) Basic regulatory control, advanced control (MPC), and optimisation, with safety systems independent
Each layer works on a different time scale.
Question 31
What is the purpose of anti-surge control on a centrifugal compressor?
- To increase surge
- To control temperature only
- To control lubricating oil
- To keep flow above the surge line by recycling or blowing off gas
Show answer & solution
Answer: (D) To keep flow above the surge line by recycling or blowing off gas
Surge causes flow reversal and damage.
Question 32
What is a typical cascade arrangement in a distillation reboiler?
- Steam flow controlling level
- Reflux controlling feed
- Pressure controlling cooling water only
- Tray temperature controller setting the steam flow controller set point
Show answer & solution
Answer: (D) Tray temperature controller setting the steam flow controller set point
Inner steam flow loop rejects steam pressure upsets.
Question 33
Why is a ratio controller used to blend gasoline components?
- To control temperature
- To control pressure only
- To keep the proportion of components constant as total flow changes
- To measure density
Show answer & solution
Answer: (C) To keep the proportion of components constant as total flow changes
Online octane analysers may trim the ratio.
Question 34
What is the main reason for using MPC in refinery units?
- To eliminate sensors
- To use on–off control
- To remove safety systems
- Handling interacting variables and constraints simultaneously
Show answer & solution
Answer: (D) Handling interacting variables and constraints simultaneously
MPC pushes units toward economic constraints.